Trouble-Shooting
The following guide is provided for trouble-shooting
and isolating common problems. It does not cover
every possible situation. Contact the ED&C Customer
Support Center at
800-843-3742
if any problem is not
resolved by these procedures.
Possible Cause
The breaker does not close. The breaker is already
closed.
Power is not available to the
Remote Close.
F1
All components
above the dashed
line are customer
supplied.
Corrective Action
Remove the close command and reapply after the
breaker has been subsequently opened and
charged. The Remote Close cannot be wired for
automatic operation.
Check that the Remote Close is wired correctly, as
shown in Figure
5.
Check that all connectors are properly seated.
Check for blown fuses.
Check that the voltage applied to the Remote Close
is within the specified range.
Remote Charge
Switch
Secondary D1sconnect Block (Draw-Out Only)
Rem Chrg
Rem Motor
Terminal Block
Remote
Remote
Chrg lnd
Chrg Op-
8
Close-
Close+
17
33
35
36
34
16
"C
c:
"
�
c:
;:
�
"
"
;:
.Q
i!!
i!!
"
rn
E
�
"'
:;:;
:;:;
J2
J3
P2
P3
"C
c:
t5
�
c:
;:
"
i!!
� �
"
?;
.Q
�
�
E
].
Remote Close
Motor Cutoff
Accessory
Switch-
(Solenoid)
(shown in breaker
Remote-Ciiarge Indicator
charged position)
Switch* (shown in
•
Switch rated at 0.5 A at 125 Vdc,
breaker charged position)
0.25 A at 250 Vdc, 5 A at 125 Vac.
Figure
5
Wiring diagram for the Motor Operator Mechanism and Remote Close accessories.