Simon® XTi Installation Guide

 

11

 

Household fire warning system (UL 985), basic system plus the 

following: 

• 

Wireless smoke sensor 60-848-02-95, TX-6010-01-1 

learned into sensor group 26. 

• 

Panel piezo beeps turned on 

• 

Control panel alarms set to on 

• 

Siren timeout set to 4 minutes or more 

• 

Trouble beeps set to on 

• 

RF jam detect set to on 

• 

Hardwired siren supervision set to on 

• 

Smoke supervision set to on 

UL 1635 digital alarm communicator system the following 

settings are required only if the system is set up for central 

station reporting: 

• 

Phone mode 1 set to “All SIA” or “All CID” 

• 

Automatic phone test set to 001 

• 

RF timeout set to 4 hours 

• 

AC power failure report set to on 

• 

CPU low battery report set to on 

• 

Fail to communicate set to on 

• 

Entry delay plus the dialer delay must not exceed 60 

seconds 

SIA system requirements 

Verified to SIA CP-01-2007 by ETL, basic system, plus if 

multiple annunciations are required, use hardwired siren 13-

046. 

Note: 

For UL 1635 installations, entry delay plus dialer abort 

delay must not exceed 60 seconds. 

Table 8 below describes programming requirements to meet 

ANSI-SIA CP-01. 

Table 8: SIA setting requirements 

 

Function 

Default setting 

Required setting 

Entry delay 

30 seconds 

30 to 240 seconds 

Exit delay 

60 seconds 

45 to 240 seconds 

Dialer delay 

30 seconds 

15 to 45 seconds 

Auto arm 

On 

On 

Un-vacated premises 

On 

On 

Call waiting 

Off 

On if reporting to 
central station and 
customer has call 
waiting service 

Alarm cancel window 

6 minutes 

6 to 255 minutes, Off 

System test 

Enabled 

Enabled 

Communication test 

Enabled 

Enabled 

Exit extension 

On 

On 

Swinger shutdown 

On (one trip) 

On (one trip) 

Function 

Default setting 

Required setting 

Fire alarm verify 

Off 

On 

Duress/panic code 

Disabled 

Disabled   

Cross zone 

Disabled 

Disabled for zones 
with high probability of 
false alarms  

Table 9 below describes nonprogrammable (hard-coded) 

system operation, as required to meet ANSI-SIA CP-01. 

Table 9: Nonprogrammable system operation   

Function 

Operation 

Silent exit 

All annunciators enabled 

Remote arming exit time and 
progress annunciation 

All annunciators enabled 

Abort annunciation 

Enabled 

Cancel report annunciation 

Enabled 

Recent closing 

Enabled (2-minute window) 

Exit error 

Enabled 

Restoration of power 

Panel resumes operation in same 
arming state and disregards alarm 
signals from sensors for the first 
60 seconds after power 
restoration 

Cancel alarm 

Enter code only 

Central station reporting 

Note

: The panel shall not be set or programmed to place a call 

to a police station number that has not been specifically 

assigned by that police station for such service. 

 

CAUTION: 

If call waiting is used on a non-call waiting line, 

successful connection to the central station may be prevented.  

ATTENTION: Si l'appel en attente est utilisé sur une ligne 
d'attente non - appel, connexion réussie à la station centrale 
peut être empêché . 

 

The panel has been tested with the following central station 

receivers using SIA and Contact ID reporting formats: 

Before beginning installation, installers must verify that the 

central station is equipped with the following receivers: 

• 

Radionics D6600 central station receiver 

• 

Sur-Gard central station receiver with models SG-DRL2A 

and SG-CPM2 

• 

CS5000 digital alarm communicator receiver 

 

 

Содержание Simon XTi

Страница 1: ...24 RF TS d 00 01 04 05 06 or 07 Simon XT Talking Touchpad 60 924 3 XT b 01 Carbon Monoxide alarm TX 6310 01 1 b 600 6520 95 b 34 a Not certified as a primary protection circuit for UL listed systems and is for supplementary use only b Has not been investigated by UL c Required for UL listed residential fire alarm applications d The TWTTS has been verified for use by ETL Neither this device nor oth...

Страница 2: ...ote Mark both mounting holes in the middle of the mounting slot This will allow better adjustment of the panel before securing it to the wall Figure 2 Mounting holes 7 Secure the mounting screws provided to the locations on the wall marked in step 6 Do not tighten the screws Leave enough clearance to mount the mounting plate Note Use wall anchors if no studs are present 8 Mount the mounting plate ...

Страница 3: ... kohm resistor as shown in Figure 4 below The resistor must be connected at the last switch in the circuit Figure 4 Normally closed hardwired reed switches Note Do not install the resistor at the panel terminals This does not provide supervision of the wire Wiring phone lines You can connect a phone line to the panel for systems monitored by a central monitoring station or systems that notify user...

Страница 4: ...latch back to remove the battery 4 Insert the new battery into the battery compartment and snap into place 5 Plug the battery connector into the panel CAUTION Do not connect the battery until you are ready to power up the panel ATTENTION Ne branchez pas la batterie tant que vous n êtes pas prêt à mettre le panneau sous tension Resetting memory to factory defaults If you need to reset memory to fac...

Страница 5: ...m Messages will also display on this icon describing what caused the alarm Press this icon to cancel the alarm Item Description These four icons depict the status of the sensors installed in your system A green check indicates sensors are closed or no recent activity detected A red exclamation indicates sensors are open or recent activity has been detected Pressing these icons will open a new scre...

Страница 6: ...ty Otherwise the default will be the Home screen and the screen will always be lit If AC power is lost the screen will go blank after 2 minutes of inactivity to maximize battery life Note The screen will automatically go blank at 2 00 am daily for 60 minutes Calibration Press the Show icon to enter the calibration screen This screen will allow you to recalibrate the touch screen Help Press the Hel...

Страница 7: ...21 This code is limited to changing all but the following Dealer code code length downloader code phone lock phone 1 phone 2 phone 1 report mode phone 2 report mode HW1 function Access codes Table 5 below describes the Access code menu programming options Table 5 Access codes Function Default Description Dealer code 4321 You can use the dealer code to program all system options including high secu...

Страница 8: ...longer beep Key fob Press the lock and unlock buttons at the same time To learn program a sensor 1 From the Programming screen enter the access code from the codes listed in Table 5 on page 7 The display shows each entered access code digit as a dot 2 Press OK You are now in the programming screen 3 Press Sensors 4 Press Learn Sensor 5 Trip the sensor see Table 6 above The Edit Sensor screen will ...

Страница 9: ...nsor testing a 1 1 or greater touch screen press the Settings gear icon scroll down and then press the RF Test icon 6 of 8 6 Press Close repeatedly to exit Sensor Test Failure If sirens do not beep when a sensor is tripped use an RF Sniffer 60 401 test tool to verify that the sensor is transmitting Constant beeps from the RF Sniffer indicate a faulty sensor Replace the sensor If possible locate se...

Страница 10: ...ition a trouble signal will be annunciated indicating that the battery may no longer support a full alarm load When fully charged the battery will operate the panel without AC power for 24 hours with the panel in a normal standby condition followed by 5 minutes in full alarm condition including the maximum specified auxiliary load of 250 mA Radio frequency 319 5 MHz Storage temperature 29 to 140ºF...

Страница 11: ...ed Communication test Enabled Enabled Exit extension On On Swinger shutdown On one trip On one trip Function Default setting Required setting Fire alarm verify Off On Duress panic code Disabled Disabled Cross zone Disabled Disabled for zones with high probability of false alarms Table 9 below describes nonprogrammable hard coded system operation as required to meet ANSI SIA CP 01 Table 9 Nonprogra...

Страница 12: ...cations Changes or modifications not expressly approved by the party responsible for compliance could void the user s authority to operate the equipment FCC Part 15 registration number B4Z 910C SIMON IC 1175C 910CSIMO This Class B digital apparatus complies with Canadian ICES 001 Cet appareil numérique de la classe B est conforme à la norme NMB 003 du Canada Part 68 This equipment complies with Pa...

Отзывы: