background image

Step 6:   Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture below. Pull on 

ends to make tight around breakers. Trim zip ties as needed and install Warning label next to release tab on zip tie at 
generator breaker. 

 

 

 

 

 

Step 7:  Re-Install panel cover, Verify proper operation of interlock. Main breaker 

ON,

 generator breaker 

OFF

 and generator breaker 

CAN NOT

 be turned on.   Generator breaker 

ON

, main breaker 

OFF

 and main breaker 

CAN NOT

 be turned on. 

 

 

 

 

 

 

   

 

 

 

 

  

   Main On 

 

 

        Generator On 

 

Place Generator start-up procedure label on panel box, Place CAUTION label on panel box and electric meter pan. 
 
The MAIN and the GENERATOR breakers should NEVER be able to be turned on at the same time.  If panel cover is removed the 
Generator breaker is NEVER to be turned on.  If for any reason the interlock does not function properly, DO NOT USE and contact us 
immediately at 

[email protected]

 for support and instructions. 

 
Thank You for your support, 
 
GenInterlock Team 

 

DISCLAIMER: 

GenInterlock.com is NOT responsible for misuse or improper 

installation. All electrical equipment should be installed and maintained by 
qualified personnel. Any consequences arising from improper use is the 
responsibility of the user.  
  

GenInterlock.com 

[email protected]

 

732-339-4191 

Отзывы: