Chapter 15
– Installation
RPV311
RPV311-TM-EN-7
235
Place the board back in the case.
Secure the case by screwing the back panel and connecting the terminals cables.
Connections shall use insulated flexible wires of 1.5 mm² cross section, 8 mm ring
terminals, and M3 holes.
Before making the electrical connection, make sure the signal is applied in
accordance with the technical specifications of the equipment. For information about
DC transducer inputs specifications, see Chapter 17: Technical Specifications.
14.1.1
Connection diagram of the DC transducer inputs of ± 10 V
Figure 124: Connection Diagram of DC Transducer Inputs ± 10 V
15
Analog DC Transducer Inputs ± 20 mA
The RA331, RA332, and RA333 modules have up to 8, 16, or 8 analog inputs,
respectively, which can be configured for measurement of currents of DC
transducers of -20 mA to 20 mA. All channels are identified of 101 to 108 for the
RA331 and RA333, and 101 to 116 for the RA332.
Each analog input has three terminals: positive voltage, positive current and negative
terminal which are used for the current and for the voltage, as shown in
To define if the driver will measure current of a DC transducer it is necessary to select
an internal jumper in the module. The binary and analog inputs are galvanically
isolated.
Figure 125: Analog Input Terminals
Содержание RPV311
Страница 2: ......
Страница 44: ......
Страница 99: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 99 Figure 46 Status monitoring sequence ...
Страница 101: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 101 Figure 47 Monitoring sequence ...
Страница 104: ...Chapter 5 Operation RPV311 104 RPV311 TM EN 7 Figure 49 Records monitoring sequence harmonics flicker and SOE ...
Страница 106: ...Chapter 5 Operation RPV311 106 RPV311 TM EN 7 Figure 50 Equipment settings monitoring sequence ...
Страница 107: ...RPV311 Chapter 5 Operation RPV311 TM EN 7 107 Figure 51 Circuit and channel settings monitoring sequence ...
Страница 108: ...Chapter 5 Operation RPV311 108 RPV311 TM EN 7 Figure 52 Relays PMU and MODBUS settings monitoring sequence ...
Страница 110: ...Chapter 5 Operation RPV311 110 RPV311 TM EN 7 Figure 53 General information monitoring sequence ...
Страница 142: ......
Страница 149: ...RPV311 Chapter 9 TW Fault Locator RPV311 TM EN 7 149 Figure 75 TW Fault Location example 1 ...
Страница 152: ......
Страница 160: ......
Страница 162: ......
Страница 164: ......
Страница 204: ......
Страница 265: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 265 Figure 142 RPV311 Dimensions ...
Страница 275: ...Chapter 17 Technical Specifications RPV311 RPV311 TM EN 7 275 Figure 143 RA331 RA332 and RA333 dimensions ...
Страница 279: ...RPV311 Appendix A Equipment Log RPV311 TM EN 7 279 ...