12
R E LI AG E A R LV MCC
LO W VO LTAG E M OTO R CO N T R O L C EN T ER
Note:
1. If anchor bolts are to be inbedded in
the foundation, they must be located according
to the drawing for the specific equipment. Locate
one in the center front and one in the center back.
Anchor bolts should be 1/2 inch diameter, of
Grade 2 steel (minimum) In non-Seismic Zone 4
Locations. Bolts must extend a minimum of 2
11/32 inch above grade to 3/4 inch above the
channel sill. If 13 (330.2mm) deep verical sections
are used, anchor bolts or some form of external
bracing
is required.
2. Seismic IBC testing was performed use 1/2' - 13
Grade 5 bolts, torqued to 50
foot-pounds, located in each of the
four corners in each section.
REF.
DIM.
Section Depth
13° Deep
20° Deep
22° Deep
25° Deep
30° Deep
Width "A"
B
C
B
C
B
C
B
C
B
C
20°
10.00°
8.73°
10.00°
15.73°
10.00°
17.73°
10.00°
20.68°
10.00°
25.69°
508.8 mm
254.4 mm
221.7 mm
254.4 mm
399.5 mm
254.4 mm
450.3 mm
254.4 mm
525.3 mm
254.4 mm
653.5 mm
24°
12.00°
8.73°
12.00°
15.73
12.00°
17.73°
12.00°
20.68°
12.00°
25.69°
609.6 mm
304.8 mm
221.1 mm
304.8 mm
399.5 mm
304.8 mm
450.3 mm
304.8 mm
525.3 mm
304.8 mm
653.5 mm
30°
15.00°
8.73°
15.00°
15.73°
15.00°
17.73°
15.00°
20.68°
15.00°
25.69°
762.0 mm
381.0 mm
221.7 mm
381.0 mm
399.5 mm
381.0 mm
450.3 mm
381.0 mm
525.3 mm
381.0 mm
653.5 mm
Indoor enclosures
Elevation and Mounting
30-inch Deep Sections 600 A to 1200 A Main Bus
—
11
—
10
—
10
End view standard
30" deep
—
11
Bottom view: Location
of mounting holes
Removable
floor
plates
2.09
[53,1]
2.16
[54,9]
C"
Front
Ø .63 [15,9]
MTG hole
23.80
[604,5]
A"
B"
12. 53
[318,3]
3.00
[76,2]
90.00
[2286,0]
5"
1 [22]
1.50 [38,1]
Front
Fan
when required
NOTICE
30.00
[762,0]
Содержание ReliaGear LV MCC