3.14.5 Data Types Mapping between PME Project and SNMP
When you configure HMI tags in a PME project and you would like to use them in SNMP communication, all of the HMI
tags are mapped to the corresponding data type in SNMP as listed in the following table. To verify this, review the
Sequence of HMI Tags
object in the MIB file.
PME VIEW Data Types
SNMP Data Types
BOOL
INTEGER
DINT
INTEGER
LREAL
DISPLAYSTRING
STRING
DISPLAYSTRING
Note
The PME VIEW LREAL data type is mapped to DISPLAYSTRING to retain the data intact.
You can continue to use the data type
override/suffix
mechanism in PME for the LREAL data type to represent a INT/DINT
if you have configured the data type for driver variables. This enables you to map to the DISPLAYSTRING data type in the
SNMP communication as well.
For example, for the GE SRTP driver, you can override the
IO Address
of LREAL variable
LREALVar
data type as %R100
[INT]. This maps LREALVar to DISPLAYSTRING in the MIB file.
3.14.6 Establish SNMP Communication
Attention
SNMP communication requires that both the QuickPanel
+
device and the SNMP
Manager running on a machine are connected on a valid Ethernet network.
➢
To establish SNMP communication with the QuickPanel
+
device
1.
Download the Project to the network connected QuickPanel
+
device and start Runtime.
2.
Configure the Trap Destinations
with the IP Address of the SNMP Manager.
Note
If you do not want to be notified of Traps, you do not need to configure Trap Destinations.
3.
Enable a SNMP Agent
.
4.
Export the MIB
to a SD Card.
5.
Auto-discover or connect the QuickPanel
+
SNMP Agent from the SNMP Manager. Once connected,
load the MIB
to the
SNMP Manager tool.
The SNMP Manager communicating with QuickPanel
+
device can query values for HMI Tags and receive
Alarms/Trap notification from the QuickPanel
+
device operating as a SNMP Agent.
Tip
�
If you get out of sequence in the steps for configuring Traps and starting the SNMP service to establish the SNMP
communication,
enable or disable
the SNMP Agent again using the QuickPanel
+
OS Utilities Setting tool.
Содержание QuickPanel+ IC755CxS06RDx
Страница 6: ...6 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 16: ...16 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 24: ...24 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 54: ...54 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 65: ...Mounting and Installation For public disclosure GFK 2847W 65 IC755CxS15CDxMounting Holes ...
Страница 87: ...Mounting and Installation For public disclosure GFK 2847W 87 IC755CxSxxCDxSD Card Location ...
Страница 88: ...88 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 96: ...96 GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 99: ...For public disclosure GFK 2847W 99 Secomea Products used with QuickPanel in Application ...
Страница 105: ...For public disclosure GFK 2847W 105 ...
Страница 112: ...GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 114: ...GFK 2847W For public disclosure QuickPanel Operator Interface User Manual Notes ...
Страница 115: ...Appendix B Orderable Part Numbers For public disclosure GFK 2847W ...
Страница 116: ......
Страница 118: ...Automation Controls 1 800 433 2682 1 434 978 5100 www geautomation com GFK 2847W For public disclosure ...