Installation Instructions

INSTALLING OPTION—FOR GE MONOGRAM

MONOGRAM INDUCTION COOKTOP
AND MONOGRAM DOWNDRAFT VENT
COMBINATION INSTALLATION ONLY.

The installation of the downdraft vent with 
this cooktop requires careful consideration. 
Both the cooktop and the vent must be installed
according to each specific installation instruction.

BASE CABINET REQUIREMENTS

The combined installation will fit in a standard 
24

deep base cabinet. Use a 30

or wider base

cabinet.

– The vent housing, blower and ductwork will

occupy the base cabinet.

COOKTOP REQUIREMENTS

The countertop must have a deep flat surface to
accommodate the cooktop and vent. Countertops
with a rolled front edge and backsplash will not
provide the flat surface area required. 

• Review the illustration to determine the countertop

surface requirements.

– All cutout clearances for this installation must 

be observed. 

22-3/8

cutout

depth

19-5/8

cooktop

cutout

depth

2-3/4

1/8

gap

1-3/4

″ 

min. cooktop

cutout to rear vertical
combustible surface

23-1/2

″ 

SS

23-3/8

″ 

Black

total flat surface

required 

at center

1-3/4

″ 

min. cutout to

wall, both sides

2-1/2

″ 

min. clearance 

to cutout

Front edge of countertop

1-1/32

″ 

cooktop overlap at center

28-1/2

″ 

cooktop and vent 

area cutout

29-7/8

″ 

SS

29-3/4

Black

3/4"

22-3/4" Inside

22" to Support Rail

2-1/2" to

Cutout

1-7/8"

3/4" 
Thick 
Support 
Rail

20-1/16"

Vent

20-3/8

Содержание Profile PHP900

Страница 1: ...UST BE HARD WIRED DIRECT WIRED INTO AN APPROVED JUNCTION BOX A PLUG AND RECEPTACLE IS NOT PERMITTED ON THESE PRODUCTS Proper installation is the responsibility of the installer and product failure due...

Страница 2: ...disconnect switch is located If you do not know have your electrician show you ELECTRICAL REQUIREMENTS This appliance must be supplied with the proper voltage and frequency and connected to an individ...

Страница 3: ...ertop must have a deep flat surface to accommodate the combined installation of the cooktop and vent Consideration must be given to the separate electrical supply locations Allow 12 clearance between...

Страница 4: ...e of countertop 19 5 8 depth of cutout 28 1 2 width of cutout 1 3 4 Min Between cutout and the wall behind the cooktop Wall coverings cabinets and countertop must withstand heat up to 200 F If a 30 cl...

Страница 5: ...t have a deep flat surface to accommodate the cooktop and vent Countertops with a rolled front edge and backsplash will not provide the flat surface area required Review the illustration to determine...

Страница 6: ...is not necessary for this combination installation If the baffle is attached remove it This cooktop is only approved to be installed over the specific models listed on the label of this unit POWER SU...

Страница 7: ...ires from the conduit through the opening of the junction box The conduit strain relief clamp must be securely attached to the junction box and the flexible conduit must be securely attached to the cl...

Страница 8: ...stainless steel models apply foam tape on the sides and rear 3 Bottom of Cooktop Cloth under Cooktop Bottom of Cooktop Foam Tape Cooktop Glass INSTALL HOLD DOWN BRACKETS Start one screw through the b...

Страница 9: ...inal check that all required clearances are met 5 Cooktop ATTACH HOLD DOWN BRACKETS TO CABINET Open the cabinet door Install the second screw through the bracket and tighten Then tighten the first scr...

Страница 10: ...oting list NOTE TO ELECTRICIAN The power leads supplied with this appliance are UL recognized for connections to larger gauge household wiring The insulation of these leads is rated at temperatures mu...

Отзывы: