70
••••
Chapter Six - Advanced Options
DDE Server User’s Guide
Adding a Register Group
Click this button to add a new register group. The
Select Register Group Type
dialog box appears:
Enter the
Register Group
name. The name may be up to 20 alphanumeric characters
and cannot include embedded spaces or special characters, such as: + * / /, ? () “ ‘.
Select the register type from the
Select Register Type
pull-down list. The
Modbus
Register Types
shown are determined by the function codes selected previously. The
four types of register groups that support some of the Modbus function codes are R0,
R1, R3, R4. The table below describes the types, registers, supported codes, and
uses.
Type
Code
Type of Register
Supported
Function Codes
Use
R0
Coils
01
Reading coil status
R0
Coils
05
Setting/forcing/
executing coils
R0
Coils
15
Setting/forcing
multiple coils
R1
Contacts or discrete
inputs
02
Reading
contact/discrete
inputs
R3
Actual value or input
register
04
Reading actual value
or input registers
R4
Setpoint or holding
register
03
Reading setpoint or
holding registers
R4
Setpoint or holding
register
06
Presetting single
setpoint register
R4
Setpoint or holding
register
16
Presetting multiple
registers
You will need the device’s Modbus RTU protocol specification for the correct codes
to add or delete.
Click
OK
to accept your new register group – the
Register Group
dialog box is
displayed for you to finish defining the characteristics of the new register group.
Содержание POWER LEADER GEH-6510
Страница 5: ...DDE Server User s Guide v This page left blank intentionally ...
Страница 35: ...DDE Server User s Guide Chapter Three Getting Started 31 This page left blank intentionally ...
Страница 68: ...DDE Server User s Guide Chapter Five Troubleshooting 65 This page left blank intentionally ...
Страница 88: ...DDE Server User s Guide Appendix A Register Addressing Conventions 85 This page left blank intentionally ...