Appendix A. Configuring Advanced User Parameters
254
PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual
GFK-2224Q
A-2
Advanced User Parameter Definitions
Note:
The RX3i CPE305/CPE310 embedded Ethernet interface does not support all AUPs listed.
AUPs that can be used with CPE305/CPE310 are indicated by a footnote. Other
PACSystems Ethernet interfaces support the use of all AUPs listed in the following table.
System Memory Parameters (task b)
Default
Range
staudp
Remote command UDP port
18245 (4745H)
1 – 65535 (ffffH)
Only the gdata_port
and gXX_udp
parameters may
share the same UDP
port number. All other
UDP port number
parameters in the AUP
file must use unique
port numbers.
stpasswd
Station Manager password (only visible from MODIFY
prompt)
“system”
0 – 8 characters, case
sensitive, no spaces
Backplane Driver Parameters (task c)
Default
Range
crsp_tout
CPU response timeout. Amount of time to wait for the
CPU to respond to a request sent through the PLC
Driver.
60 seconds
10 – 3600 (E10H)
chct_comp
HCT compatibility option. (Rel 2.57 and later) Allows
Ethernet interface to ignore SRTP header errors
(typically generated by remote HCT devices) that
were not detected in previous Series 90 products.
0 = HCT compatibility disabled (= report all errors)
1 = HCT compatibility enabled (= ignore some errors)
0 (0H)
0, 1
cstorm
COMMREQ storm onset threshold. Establishes a
number of COMMREQs per second at or above which
the PLC application is considered to be sending
COMMREQs so rapidly that the Ethernet interface
cannot continue normal operation. Setting this
parameter to 0 disables COMMREQ storm error
detection.
500 (01F4H)
0 – 10,000 (2710H)
cnostorm
COMMREQ storm end threshold. Establishes the
number of COMMREQs per second at or below which
the COMMREQ storm condition (see above) is
considered to have ended. If the
cstorm
parameter is
not set to 0, this parameter should always be less
than
cstorm
. If
cstorm
is set to 0, this parameter is
ignored.
100 (0064H)
0 – 10,000 (2710H)
RDS Parameters (task d)
None
None
26
Supported by RX3i CPE305 and CPE310 models.
Содержание PACSystems RX7i
Страница 45: ......
Страница 54: ...Chapter 4 Configuration GFK 2224Q January 2017 41 Figure 18 CPE400 Advanced Ethernet Configuration LAN1 LAN 2 ...
Страница 80: ...Chapter 4 Configuration GFK 2224Q January 2017 67 ...
Страница 81: ......
Страница 122: ...Chapter 6 Programming EGD Commands GFK 2224Q January 2017 109 ...
Страница 142: ...Chapter 7 Programming SRTP Channel Commands GFK 2224Q January 2017 129 Figure 51 Sample Ladder Logic for COMMREQ ...
Страница 147: ......
Страница 193: ...Chapter 10 OPC UA Server 180 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q Example ...
Страница 202: ...Chapter 10 OPC UA Server GFK 2224Q January 2017 189 Figure 73 Machine Edition Online Command to Set Passwords ...
Страница 211: ......
Страница 253: ...Chapter 12 Diagnostics 240 PACSystems RX7i RX3i TCP IP Ethernet Communications User Manual GFK 2224Q ...
Страница 262: ...Chapter 13 Network Administration GFK 2224Q January 2017 249 ...
Страница 263: ......