Status Address, Length:
The Status Address is the reference memory location for the 32 bits of status data
associated with the PROFINET Controller itself. The Status address can be assigned to valid %I, %Q, %R, %AI,
%AQ, %W, %G, %T or %M memory by right-clicking on the
Status Address
field and selecting the
Data Entry
tool. The default value is the next available %I address. See Chapter 5
, for definitions of the status
bits that the module writes to this address.
Figure 42: Setting the Status Reference Address
Note:
Because point faults are not supported by %G, %T and %M, the other available memory types, or I/O
Symbolics, are preferred.
SFP Cage 1 / 2 / 3 / 4:
If the PNC001module will use plug
–
in Small Form-factor Pluggable devices in Port 3
and/or Port 4, specify the SFP devices in the appropriate field(s). On the
Settings
tab, right-click in the Values
field for the port, and select
Data Entry
tool to open the Catalog window. In the Catalog window, select the
type of SFP device for the port, as shown in Figure 43, and click OK. If the device is not listed, choose
GENERIC_SFP
to add it to the configuration.
Figure 43: Select SFP Device from Catalog