Chapter
GFK-2746
Chapter Chapter
1 Introduction
Chapter
1-39
1
The Profibus network module also supports DPV1 service. The details are as below:
DPV1 Write service
Slot#=0, Index 1: Write STXPBS001 extension parameter(2Byte)
Slot#0~31, Index 1: Write parameter for an IO module.
Slot#0~31, Index 2: Write memory data to an IO module.
Slot#= 254: Write user data to EEPROM user area
Index=0~127(Offset in EEPROM user area)
Data Ln=Length for data to be written
Data [0] ~Data[n] =User data
List of valid commands for (Slot#=0, Index 1: Write STXPBS001 extension parameter (2
bytes). Note that the length of parameter may vary depending upon the module chosen for
STXPBS* Network adapter with Integrated IO modules and hence the command word.
Command
Reaction to
Bus Fault
DP Clear Action
Word data
Format
Restart on Bus
fault
Hex
Binary
00 00
00000000
00000000
00: Profibus
communication
00: Bus Stop IO
fault action
00:INTEL
00:Power reset
00 10
00000000
00010000
00: Profibus
communication
00: Bus Stop IO
fault action
00:INTEL
01: auto reset
01 00
00000001
00000000
00: Profibus
communication
00: Bus Stop IO
fault action
01:MOTOROLA
00:Power reset
01 10
00000001
00010000
00: Profibus
communication
00: Bus Stop IO
fault action
01:MOTOROLA
01: auto reset
00 04
00000000
00000100
00: Profibus
communication
01: Bus Run (
clear Output)
00:INTEL
00:Power reset
00 14
00000000
00010100
00: Profibus
communication
01: Bus Run (
clear Output)
00:INTEL
01: auto reset
01 04
00000001
00000100
00: Profibus
communication
01: Bus Run (
clear Output)
01:MOTOROLA
00:Power reset
01 14
00000001
00010100
00: Profibus
communication
01: Bus Run (
clear Output)
01:MOTOROLA
01: auto reset
00 08
00000000
00001000
00: Profibus
communication
10: Bus Run (
Hold Output)
00:INTEL
00:Power reset
00 18
00000000
00011000
00: Profibus
communication
10: Bus Run (
Hold Output)
00:INTEL
01: auto reset
01 08
00000001
00001000
00: Profibus
communication
10: Bus Run (
Hold Output)
01:MOTOROLA
00:Power reset
01 18
00000001
00011000
00: Profibus
communication
10: Bus Run (
Hold Output)
01:MOTOROLA
01: auto reset
00 01
00000000
00000001
01: Clear Input
data
00: Bus Stop IO
fault action
00:INTEL
00:Power reset
00 11
00000000
00010001
01: Clear Input
data
00: Bus Stop IO
fault action
00:INTEL
01: auto reset
01 01
00000001
00000001
01: Clear Input
data
00: Bus Stop IO
fault action
01:MOTOROLA
00:Power reset
Содержание PACSystems RSTi
Страница 4: ......
Страница 6: ......
Страница 12: ......
Страница 105: ...GFK 2746 Chapter Chapter 1 Introduction 5 5 5 Page 2 Click Next...
Страница 109: ...GFK 2746 Chapter Chapter 1 Introduction 5 9 5 Page 8 Click Finish when the install is completed...
Страница 134: ...5 34 RSTi Network Adapter Manual User Manual January 2012 GFK 2746 5 IO Figure 61 Properties window IO module...
Страница 139: ...GFK 2746 Chapter Chapter 1 Introduction 5 39 5 Figure 63 Viewing Documentation output...
Страница 170: ......