10-2
W650 Wind Generator Protection System
GEK-113032A
10.1 INTRODUCTION
10 BOOTCODE AND FIRMWARE UPGRADE
10
10.1.1 COMMUNICATION PARAMETERS
Before proceeding with the upgrade process, the following points should be taken into account:
Type of Ethernet connection:
Upgrade requires Ethernet communications.
It is highly recommended to use a direct connection between the PC and the relay using a crossed-over RJ45 Ethernet
cable, instead of using an indirect connection through a hub or switch.
Relay IP address:
It is necessary to assign a valid IP address to the relay in the Ethernet parameters via HMI in the “Product Setup >
Communication > Ethernet > Ethernet 1” menu or via EnerVista 650 Setup in “Setpoint > Product Setup>Communication
Settings > Network (Ethernet) 1” as shown in Table 10–1:
Table 10–1: ETHERNET PARAMETERS
If the relay is connected to an Ethernet network, check that the IP address is unique in order to avoid collisions.
In the case of relay that has upgraded previously its Bootcode (Sections 2), the IP address already has been assigned in
the previous process (see Figure 10–14:).
For example, if the relay settings are:
IP address: 192.168.37.240,
Netmask: 255.255.255.0 and
Gateway: 192.168.37.10.
The computer settings have to follow the pattern:
IP address: 192.168.37.XXX
Netmask: 255.255.255.0 and
Gateway: 192.168.37.10 (if desired).
XXX is a number between 0 and 255 that is not assigned to any other device to avoid collisions.
If there are not TCP/IP settings according to this pattern in the computer, it should be added (in order to communicate with
the relay) following these steps:
PRODUCT SETUP>COMMUNICATION SETTINGS >NETWORK (ETHERNET) 1
Name
Value
Units
Range
IP Address Oct1
192
[0 : 255]
IP Address Oct2
168
[0 : 255]
IP Address Oct3
37
[0 : 255]
IP Address Oct4
240
[0 : 255]
Netmask Oct1
255
[0 : 255]
Netmask Oct2
255
[0 : 255]
Netmask Oct3
255
[0 : 255]
Netmask Oct4
0
[0 : 255]
Gateway IP Oct1
192
[0 : 255]
Gateway IP Oct2
168
[0 : 255]
Gateway IP Oct3
37
[0 : 255]
Gateway IP Oct4
10
[0 : 255]
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...