GEK-113032A
W650 Wind Generator Protection System
1-17
1 GETTING STARTED
1.4 W650 HARDWARE
1
1.4W650 HARDWARE
1.4.1 MOUNTING & WIRING
Please refer to Chapter 3. Hardware for detailed mounting and wiring instructions.
1.4.2 W650 COMMUNICATIONS
The Enervista 650 Setup software communicates to the relay via the faceplate RS232 port or the rear RS485/Ethernet
ports. To communicate via the faceplate RS232 port, a standard “straight-through” serial cable is used. The DB-9 male end
is connected to the relay and the DB-9 or DB-25 female end is connected to the PC COM1 or COM2 port as described in
Figure 1–16:.
To communicate through the W650 rear RS485 port from a PC RS232 port, the GE Multilin RS232/RS485 converter box is
required. This device (catalog number F485) connects to the computer using a “straight-through” serial cable. A shielded
twisted-pair (20, 22 or 24 AWG according to American standards; 0.25, 0.34 or 0.5 mm2 according to European standards)
connects the F485 converter to the W650 rear communication port.
In order to minimize communication errors that could be caused by external noise, it is recommended to use a shielded
twist pair. In order to avoid loops where external currents could flow, the cable shield must be grounded only at one end.
The converter box (-, +, GND) terminals are connected to the relay (SDA, SDB, GND) terminals respectively. For long
communications cables (longer than 1 km), the RS485 circuit must be terminated in an RC network (i.e. 120 ohm, 1 nF).
This circuit is shown on Figure 1–17: RS485 CONNECTION FOR 650 UNITS, associated to text Zt(*).
Figure 1–16: RELAY- PC CONNECTION FOR RS232 FRONT PORT
To minimize errors from noise, the use of shielded twisted pair wire is recommended. For correct operation, polarity must
be respected, although a different polarity will not damage the unit. For instance, the relays must be connected with all
RS485 SDA terminals connected together, and all SDB terminals connected together. This may result confusing
sometimes, as the RS485 standard refers only to terminals named “A” and “B”, although many devices use terminals
named “+” and “-“.
As a general rule, terminals “A” should be connected to terminals “-“, and terminals “B” to “+”. The GND terminal should be
connected to the common wire inside the shield, when provided. Otherwise, it should be connected to the shield. Each
relay should also be daisy chained to the next one in the link. A maximum of 32 relays can be connected in this manner
without exceeding driver capability. For larger systems, additional serial channels must be added. It is also possible to use
commercially available repeaters to increase the number of relays on a single channel to more than 32. Do not use other
connection configurations different to the recommended.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...