5-76
W650 Wind Generator Protection System
GEK-113032A
5.5 CONTROL ELEMENTS
5 SETTINGS
5
5.5.4 AUTORECLOSE (79)
5.5.4.1 INTRODUCTION
Note:
The Switchgear element used in the W650 autoreclose element is the one configured in the
Number of Switchgear
setting inside
Breaker settings
, at “
Setpoint > System Setup > Breaker > Breaker settings
”. Configuration of these
Switchgear parameters is performed at
Setpoint > Relay Configuration > Switchgear
using the EnerVista 650 Setup
software.
The W650 autoreclose element allows producing up to four breaker “shots” prior to lockout. Thanks to the great flexibility of
the W650 configurable logic, the conditions to produce the autoreclose initiation and the selection of which protection
elements will be enabled after each shot can be programmed. This flexibility allows implementing protection schemes that
used to require wiring and special functions in conventional equipments. One application is, for instance, to program as
instantaneous the first protection trip and the second one to be time delayed, in order to give time for output fuses to
burning of a feeder branch. This can be as simple as disabling the instantaneous elements after the first shot using the
programmable logic. (see example in section 5.5.4.6)
5.5.4.2 MAIN AUTORECLOSE SETTINGS
Setpoint > Control Elements > Autoreclose
Table 5–71: 79 ELEMENT SETTINGS
Autoreclose settings description:
Function:
This setting allows enabling or disabling the autoreclose operation. If this setting is adjusted as
DISABLED, the recloser will be out of service.
Max Number Shots:
This setting specifies the number of autoreclose shots allowed in the element. If this number is
exceeded, the autoreclose goes to LOCKOUT status, and the fault is considered to be permanent.
Dead Time 1 ... 4:
These times correspond to the first, second, third and fourth breaker reclosings configured in the
element.
Reclaim Time
(also known as
safety time
or
reset lockout delay
)
:
This is the time required to go from LOCKOUT
to READY status once the breaker is closed.
Cond. Permission:
This setting enables the verification of the relay reclose conditions. If this setting is enabled, before
the breaker closing command execution the system will verify the possible reclose conditions. If this
setting is disabled, the closing command will be executed after the reclose time without verifying
these conditions. The reclose conditions input is configured as AR CONDS INPUT at
Setpoint >
Relay Configuration > Protection Elements
Hold Time:
This setting indicates the waiting time for the reclose conditions to be present. This setting is only
operative if the
Cond. Permission
setting is enabled.
Reset Time:
This is the time that the autoreclose takes to return to READY status after a successful reclose. Once
this time has expired, the shot counter will reset and the autoreclose will get to READY.
SETPOINT > CONTROL ELEMENTS > AUTORECLOSE
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP
RANGE
Function permission
Function
DISABLED
N/A
[DISABLED – ENABLED]
Maximum Number of shots
Max Number Shots
1
N/A
[1 : 4]
Dead time 1
Dead Time 1
0.00
0.01 s
[0.00 : 900.00]
Dead time 2
Dead Time 2
0.00
0.01 s
[0.00 : 900.00]
Dead time 3
Dead Time 3
0.00
0.01 s
[0.00 : 900.00]
Dead time 4
Dead Time 4
0.00
0.01 s
[0.00 : 900.00]
Reclaim time or reset lockout delay
Reclaim Time
0.00
0.01 s
[0.00 : 900.00]
Reclose conditions permission
Cond. Permission
DISABLED
N/A
[DISABLED – ENABLED]
Hold time
Hold Time
0.00
0.01 s
[0.00 : 900.00]
Reset time
Reset Time
0.00
0.01 s
[0.00 : 900.00]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED – ENABLED]
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...