7–72
PQM POWER QUALITY METER – INSTRUCTION MANUAL
MODBUS MEMORY MAP
CHAPTER 7: MODBUS COMMUNICATIONS
7.3.4
Memory Map
Data Formats
Table 7–11: Memory Map Data Formats (Sheet 1 of 20)
CODE
DESCRIPTION
BITMASK
F1
UNSIGNED INTEGER - NUMERICAL DATA
FFFF
F2
SIGNED INTEGER - NUMERICAL DATA
FFFF
F3*
UNSIGNED LONG INTEGER - NUMERICAL DATA
FFFFFFFF
F4*
SIGNED LONG INTEGER - NUMERICAL DATA
FFFFFFFF
F5
HARDWARE VERSION CODE
FFFF
1 = A
---
2 = B
---
↓
Ø
26 = Z
---
F6
UNSIGNED INTEGER - CURRENT KEY PRESS
FFFF
0000 = no key
---
FE01 = STORE
---
FE02 = SETPOINT
---
FE04 = MESSAGE RIGHT
---
FE08 = VALUE UP
---
FD01 = RESET
---
FD02 = MESSAGE LEFT
---
FD04 = MESSAGE UP
---
FD08 = VALUE DOWN
---
FB01 = ACTUAL
---
FB02 = MESSAGE DOWN
---
*
Refer to section A.7 - Reading Long Integers From Memory Map - for more information.
Содержание Multilin PQM
Страница 3: ...Courtesy of NationalSwitchgear com ...
Страница 4: ...Courtesy of NationalSwitchgear com ...
Страница 10: ...TOC VI PQM POWER QUALITY METER INSTRUCTION MANUAL TABLE OF CONTENTS Courtesy of NationalSwitchgear com ...