MIGII Digital Protection for Electrical Machines
13-1
13 TROUBLESHOOTING GUIDE
13.1 MIGII TROUBLESHOOTING GUIDE
13
13 TROUBLESHOOTING GUIDE 13.1MIGII TROUBLESHOOTING GUIDE
MIGII units have been designed and verified using the most advanced and reliable equipment. Mounting and testing
automation ensure a high consistency of the final product. Before sending a unit back to the factory, we strongly
recommend you follow the recommendations below.
Even if it will not always solve the problem, at least they will help define it better for a quicker repair.
If you need to send a unit back to the factory for repair, please use the appropriate RETURN MATERIAL
AUTHORISATION process, and follow the shipping instructions provided by our Service Department, especially in the
case of international shipments. This will lead to a faster and efficient solution of your problem.
CATEGORY
SYMPTOM
POSSIBLE CAUSE
RECOMMENDED ACTION
Protection
The relay does not trip
- Element not enabled
- Output not assigned
- Inappropriate setting group
-Set the element permission to ENABLE
Program the output to the desired element
using ENERVISTA MII SETUP-
SETPOINT-RELAY CONFIGURATION
- Make sure that desired group is active
(group 1 or group 2) and/or that there is no
settings group change input that could
modify the active group
General
When feeding the unit, no
indicator is light up
- Insufficient power supply
- Fused fuse
- Loose fuse
- Incorrect wiring
- Verify the voltage level using a multimeter
in the power supply terminals, and check
that it is within the model range.
- Remove the power supply board and
replace the fuse.
Communications
The relay does not
communicate via the front
RS232 port
- Incorrect cable
- Damaged cable
- Relay or PC not grounded
- Incorrect baud rate, port, address,
etc
- Make sure you are using a straight cable.
- Replace the cable
- Ensure ground connection
- Make sure that the communication
parameters in the computer match the
ones in the relay.
The relay does not
communicate via the
RS485 port
- Relay or PC not grounded
- Incorrect polarity
- Incorrect baud rate, address etc
- Ensure ground connection
- Invert polarity
- Test other baud rate, etc
Содержание Multilin MIGII
Страница 2: ......
Страница 114: ...5 24 MIGII Digital Protection for Electrical Machines GEK 113188A 5 4 TIME SYNCHRONIZATION 5 SETTINGS 5 ...
Страница 136: ...8 8 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 137: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 9 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 138: ...8 10 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 139: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 11 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 140: ...8 12 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 141: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 13 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 142: ...8 14 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 143: ...GEK 113188A MIGII Digital Protection for Electrical Machines 8 15 8 KEYPAD AND DISPLAY 8 4 OPERATIONS 8 ...
Страница 144: ...8 16 MIGII Digital Protection for Electrical Machines GEK 113188A 8 4 OPERATIONS 8 KEYPAD AND DISPLAY 8 ...
Страница 200: ...A 10 MIGII Digital Protection for Electrical Machines GEK 113188A A 6 MIGII THERMAL CURVES APPENDIXA A ...
Страница 208: ...B 8 MIGII Digital Protection for Electrical Machines GEK 113188A B 2 ANSI CURVES APPENDIXB B Figure B 4 ANSI INVERSE ...
Страница 230: ...C 20 MIGII Digital Protection for Electrical Machines GEK 113188A C 8 MODBUS MAP STATUS APPENDIXC C ...