5-104
G650 Generator Protection & Control System
GEK-113285A
5.6 INPUTS/OUTPUTS
5 SETTINGS
5
5.6.2 CONTROL SETTINGS FOR INPUTS/OUTPUTS
Configuration of settings relative to inputs and outputs can only be accessed through the EnerVista 650 Setup
software, and not via the HMI
. For this purpose, the user must access
Setpoint > Inputs/Outputs > Contact I/O > Board
X
, being X the corresponding I/O board.
settings relative to I/O boards are described in Table 5–101:
Table 5–101: I/O BOARD SETTINGS
The snapshot event setting enables or disables the snapshot event generation for this element. It is mandatory to enable
this setting in order the input/output values to be refreshed in IEC61850 protocol
.
Being:
X
F, G, H or J, the I/O board name, depending on the Relay model.
F and G are internal Relay boards, and H and J are additional boards available in CIO modules (remote Bus CAN I/O
module).
SETPOINT > INPUTS/OUTPUTS > CONTACT I/O >
BOARD F > BOARD G > BOARD H > BOARD J
SETTING DESCRIPTION
NAME
DEFAULT
VALUE
STEP RANGE
I/O board type (available only for CIO modules)
I/O Board Type_
X
NONE
N/A
[NONE,
16 INP + 8OUT,
8 INP + 8OUT + SUPV,
32 INP
16 INP + 8 ANA]
Input activation voltage threshold Group A
Voltage Threshold A_
X
80
1 V
[10 : 230]
Input activation voltage threshold Group B
Voltage Threshold B
_X
80
1 V
[10 : 230]
Input activation voltage threshold Group C
Voltage Threshold C_
X
80
1 V
[10 : 230]
Input activation voltage threshold Group D
Voltage Threshold D
_X
80
1 V
[10 : 230]
Debounce time for Group A
Debounce Time A
_X
15
1 ms
[1 : 50]
Debounce time for Group B
Debounce Time B
_X
15
1 ms
[1 : 50]
Debounce time for Group C
Debounce Time C
_X
15
1 ms
[1 : 50]
Debounce time for Group D
Debounce Time D
_X
15
1 ms
[1 : 50]
Input type
Input Type_
X
_CC
Y
(CC
Y
)
POSITIVE
N/A
[POSITIVE-EDGE,
NEGATIVE-EDGE,
POSITIVE,
NEGATIVE]
Input signal time delay
Delay Input Time_
X
_CC
Y
(CC
Y
)
0
1 ms
[0 : 60000]
Output logic type
Output Logic_
X
_0
Z
POSITIVE
N/A
[POSITIVE,
NEGATIVE]
Output type
Output Type_
X
_0
Z
NORMAL
N/A
[NORMAL,
PULSE,
LATCH]
Output pulse length
Pulse Output Time_
X
_0
Z
10000
1 ms
[0 : 60000]
Analog Inputs Range
Range_
X
_0
Z
NONE
N/A
[NONE,
-1 to 0mA,
0 to 1 mA,
-1 to 1 mA,
0 to 5 mA,
0 to 10 mA]
Minimum Value
Min_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Maximum Value
Max_Value_
X
_0
Z
0.00
0.01
[ -9999.99 : 9999.99]
Snapshot event generation
Snapshot Events
ENABLED
N/A
[DISABLED –
ENABLED]
Содержание Multilin G650
Страница 9: ...8 G650 Generator Protection Control System GEK 113285A TABLE OF CONTENTS ...
Страница 29: ...1 20 G650 Generator Protection Control System GEK 113285A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 293: ...5 150 G650 Generator Protection Control System GEK 113285A 5 9 LOGIC CONFIGURATION PLC EDITOR 5 SETTINGS 5 ...
Страница 391: ...11 6 G650 Generator Protection Control System GEK 113285A 11 4 RELAY CONFIGURATION 11 FREQUENTLY ASKED QUESTIONS 11 ...
Страница 426: ...GEK 113285A G650 Generator Protection Control System A 31 APPENDIX A A 1 LOGIC OPERANDS A ...
Страница 427: ...A 32 G650 Generator Protection Control System GEK 113285A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 587: ...C 22 G650 Generator Protection Control System GEK 113285A C 8 ANALOG INPUTS APPENDIXC C ...
Страница 595: ...D 8 G650 Generator Protection Control System GEK 113285A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 606: ...GEK 113285A G650 Generator Protection Control System E 11 APPENDIX E E 1 FACTORY DEFAULT LOGIC E ...
Страница 607: ...E 12 G650 Generator Protection Control System GEK 113285A E 1 FACTORY DEFAULT LOGIC APPENDIXE E ...
Страница 639: ...G 2 G650 Generator Protection Control System GEK 113285A G 1 GE MULTILIN WARRANTY APPENDIXG G ...