GE Multilin
G60 Generator Protection System
A-1
APPENDIX A
A.1 PARAMETER LISTS
A
Appendices
APPENDIX A FlexAnalog and FlexInteger ParametersA.1Parameter Lists
A.1.1 FLEXANALOG ITEMS
A FlexAnalog parameter is an analog parameter.
FlexAnalog items are also viewable in a web browser. Enter the IP address of the UR, access the
Device Information
Menu
option, then the
FlexAnalog Parameter Listing
option. Entries displayed online depend on order code.
Table A–1: FLEXANALOG DATA ITEMS (Sheet 1 of 27)
ADDRESS
FLEXANALOG NAME
UNITS
DESCRIPTION
5728
Stator Diff Iad
Amps
Stator differential phase A current (Iad)
5730
Stator Rest Iar
Amps
Stator restraint phase A current (Iar)
5732
Stator Diff Ibd
Amps
Stator differential phase B current (Ibd)
5734
Stator Rest Ibr
Amps
Stator restraint phase B current (Ibr)
5736
Stator Diff Icd
Amps
Stator differential phase C current (Icd)
5738
Stator Rest Icr
Amps
Stator restraint phase C current (Icr)
5740
Stator Diff CT Prim.
Volts
Stator differential CT primary
5744
Stator Gnd Vn 3rd
Volts
Stator ground Vn third harmonic voltage
5746
Stator Gnd Vn+V0 3rd
Volts
Stator ground Vn+V0 third harmonic voltage
5748
Stator Gnd V0 3rd
Volts
Stator ground V0 third harmonic voltage
5752
Sh Injection Voltage
Volts
Subharmonic injection voltage
5754
Sh Injection Current
Amps
Subharmonic injection current
5756
Stat Gnd Resistance
Ohms
Stator ground resistance
5759
SH Current Angle
Degrees
Subharmonic injection current angle
5760
Sns Dir Power 1
Watts
Sensitive directional power 1 actual value
5762
Sns Dir Power 2
Watts
Sensitive directional power 2 actual value
5792
RGF 1 Igd Mag
Amps
Restricted ground fault 1 differential ground current magnitude
5794
RGF 1 Igr Mag
Amps
Restricted ground fault 1 restricted ground current magnitude
5796
RGF 2 Igd Mag
Amps
Restricted ground fault 2 differential ground current magnitude
5798
RGF 2 Igr Mag
Amps
Restricted ground fault 2 restricted ground current magnitude
5800
RGF 3 Igd Mag
Amps
Restricted ground fault 3 differential ground current magnitude
5802
RGF 3 Igr Mag
Amps
Restricted ground fault 3 restricted ground current magnitude
5804
RGF 4 Igd Mag
Amps
Restricted ground fault 4 differential ground current magnitude
5806
RGF 4 Igr Mag
Amps
Restricted ground fault 4 restricted ground current magnitude
5808
RGF 5 Igd Mag
Amps
Restricted ground fault 5 differential ground current magnitude
5810
RGF 5 Igr Mag
Amps
Restricted ground fault 5 restricted ground current magnitude
5812
RGF 6 Igd Mag
Amps
Restricted ground fault 6 differential ground current magnitude
5814
RGF 6 Igr Mag
Amps
Restricted ground fault 6 restricted ground current magnitude
5856
Freq Rate 1 Value
Hz/s
Frequency rate of change 1 actual value
5860
Freq Rate 2 Value
Hz/s
Frequency rate of change 2 actual value
5864
Freq Rate 3 Value
Hz/s
Frequency rate of change 3 actual value
5868
Freq Rate 4 Value
Hz/s
Frequency rate of change 4 actual value
6144
SRC 1 Ia RMS
Amps
Source 1 phase A current RMS
6146
SRC 1 Ib RMS
Amps
Source 1 phase B current RMS
6148
SRC 1 Ic RMS
Amps
Source 1 phase C current RMS
6150
SRC 1 In RMS
Amps
Source 1 neutral current RMS
6152
SRC 1 Ia Mag
Amps
Source 1 phase A current magnitude
6154
SRC 1 Ia Angle
Degrees
Source 1 phase A current angle
6155
SRC 1 Ib Mag
Amps
Source 1 phase B current magnitude
6157
SRC 1 Ib Angle
Degrees
Source 1 phase B current angle
6158
SRC 1 Ic Mag
Amps
Source 1 phase C current magnitude
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...