GE Multilin
G60 Generator Protection System
5-301
5 SETTINGS
5.8 INPUTS/OUTPUTS
5
Remote outputs (1 to 32) are FlexLogic operands inserted into GSSE/GOOSE messages that are transmitted to remote
devices on a LAN. Each digital point in the message must be programmed to carry the state of a specific FlexLogic oper-
and. The above operand setting represents a specific DNA function (as shown in the following table) to be transmitted.
b) USERST BIT PAIRS
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE OUTPUTS UserSt BIT PAIRS
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote
Devices section.
5.8.9 RESETTING
PATH: SETTINGS
INPUTS/OUTPUTS
RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or any
programmed operand.
When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
RESET OP
FlexLogic operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON)
,
RESET OP (COMMS)
or
RESET OP (OPERAND)
to identify the source of the command. The setting
shown above selects the operand that will create the
RESET OP (OPERAND)
operand.
Table 5–34: IEC 61850 DNA ASSIGNMENTS
DNA
IEC 61850 DEFINITION
FLEXLOGIC OPERAND
1
Test
IEC 61850 TEST MODE
2
ConfRev
IEC 61850 CONF REV
REMOTE OUTPUTS
UserSt- 1 BIT PAIR
UserSt- 1 OPERAND:
Off
Range: FlexLogic operand
MESSAGE
UserSt- 1 EVENTS:
Disabled
Range: Disabled, Enabled
RESETTING
RESET OPERAND:
Off
Range: FlexLogic operand
NOTE
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...