5-186
G60 Generator Protection System
GE Multilin
5.6 GROUPED ELEMENTS
5 SETTINGS
5
d) PHASE INSTANTANEOUS OVERCURRENT
(ANSI 50P, IEC PIOC)
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
PHASE CURRENT
PHASE IOC 1(2)
The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as a
definite time element. The input current is the fundamental phasor magnitude. For timing curves, see the publication Instan-
taneous Overcurrent Element Response to Saturated Waveforms in UR-Series Relays (
Figure 5–86: PHASE INSTANTANEOUS OVERCURRENT 1 SCHEME LOGIC
PHASE IOC1
PHASE IOC1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
PHASE IOC1 SIGNAL
SOURCE: SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
MESSAGE
PHASE IOC1
PICKUP: 1.000
pu
Range: 0.000 to 30.000 pu in steps of 0.001
MESSAGE
PHASE IOC1 PICKUP
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PHASE IOC1 RESET
DELAY: 0.00
s
Range: 0.00 to 600.00 s in steps of 0.01
MESSAGE
PHASE IOC1 BLOCK A:
Off
Range: FlexLogic operand
MESSAGE
PHASE IOC1 BLOCK B:
Off
Range: FlexLogic operand
MESSAGE
PHASE IOC1 BLOCK C:
Off
Range: FlexLogic operand
MESSAGE
PHASE IOC1
TARGET: Self-reset
Range: Self-reset, Latched, Disabled
MESSAGE
PHASE IOC1
EVENTS: Disabled
Range: Disabled, Enabled
827033A8.CDR
AND
AND
AND
SETTING
1 = Enabled
Function
SETTING
= IA
Source
= IC
SETTINGS
= Off
Block A
= Off
Block B
= Off
Block C
SETTING
Pickup
RUN
IA > Pickup
RUN
IB > Pickup
RUN
IC > Pickup
= IB
SETTINGS
Pickup Delay
T
PKP
T
RST
Reset Delay
T
PKP
T
RST
T
PKP
T
RST
OR
FLEXLOGIC OPERANDS
PHASE IOC1 A PKP
PHASE IOC1 A DPO
PHASE IOC1 B PKP
PHASE IOC1 B DPO
PHASE IOC1 C PKP
PHASE IOC1 C DPO
PHASE IOC1 PKP
FLEXLOGIC OPERAND
PHASE IOC1 A OP
PHASE IOC1 B OP
PHASE IOC1 C OP
FLEXLOGIC OPERANDS
OR
PHASE IOC1 OP
FLEXLOGIC OPERAND
AND
PHASE IOC1 DPO
FLEXLOGIC OPERAND
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...