5 SETTINGS
5.5 FLEXLOGIC
5
5.5.2 FLEXLOGIC RULES
When forming a FlexLogic equation, the sequence in the linear array of parameters must follow these general rules:
1.
Operands must precede the operator which uses the operands as inputs.
2.
Operators have only one output. The output of an operator must be used to create a virtual output if it is to be used as
an input to two or more operators.
3.
Assigning the output of an operator to a virtual output terminates the equation.
4.
A timer operator (for example, "TIMER 1") or virtual output assignment (for example, " = Virt Op 1") may only be used
once. If this rule is broken, a syntax error will be declared.
Table 5–16: FLEXLOGIC GATE CHARACTERISTICS
GATES
NUMBER OF INPUTS
OUTPUT IS ‘1’ (= ON) IF...
NOT
1
input is ‘0’
OR
2 to 16
any input is ‘1’
AND
2 to 16
all inputs are ‘1’
NOR
2 to 16
all inputs are ‘0’
NAND
2 to 16
any input is ‘0’
XOR
2
only one input is ‘1’
Table 5–17: FLEXLOGIC OPERATORS
TYPE
SYNTAX
DESCRIPTION
NOTES
Editor
INSERT
Insert a parameter in an equation list.
DELETE
Delete a parameter from an equation list.
End
END
The first END encountered signifies the last entry in
the list of processed FlexLogic parameters.
One-shot
POSITIVE ONE SHOT One shot that responds to a positive going edge.
A ‘one shot’ refers to a single input gate
that generates a pulse in response to an
edge on the input. The output from a ‘one
shot’ is True (positive) for only one pass
through the FlexLogic equation. There is a
maximum of 64 ‘one shots’.
NEGATIVE ONE
SHOT
One shot that responds to a negative going edge.
DUAL ONE SHOT
One shot that responds to both the positive and
negative going edges.
Logic
gate
NOT
Logical NOT
Operates on the previous parameter.
OR(2)
↓
OR(16)
2 input OR gate
↓
16 input OR gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
AND(2)
↓
AND(16)
2 input AND gate
↓
16 input AND gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
NOR(2)
↓
NOR(16)
2 input NOR gate
↓
16 input NOR gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
NAND(2)
↓
NAND(16)
2 input NAND gate
↓
16 input NAND gate
Operates on the 2 previous parameters.
↓
Operates on the 16 previous parameters.
XOR(2)
2 input Exclusive OR gate
Operates on the 2 previous parameters.
LATCH (S,R)
Latch (set, reset): reset-dominant
The parameter preceding LATCH(S,R) is
the reset input. The parameter preceding
the reset input is the set input.
Timer
TIMER 1
↓
TIMER 32
Timer set with FlexLogic timer 1 settings.
↓
Timer set with FlexLogic timer 32 settings.
The timer is started by the preceding
parameter. The output of the timer is
TIMER #.
Assign
virtual
output
= Virt Op 1
↓
= Virt Op 96
Assigns previous FlexLogic operand to virtual
output 1.
↓
Assigns previous FlexLogic operand to virtual
output 96.
The virtual output is set by the preceding
parameter
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...