CHAPTER 6: SETPOINTS
S5 INPUTS/OUTPUTS
350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
6–141
Auxiliary Output
Relays 3 to 6
The 350 relay is equipped with four auxiliary output relays numbered from 3 to 6. All these
relays are available for selection for operation of protection, control, or maintenance
features. Each auxiliary relay can be selected as either
Self-Reset
, or
Latched
. If the Self-
Reset type is selected, the output relay will be energized as long as the element is in
operating mode and will reset when the element drops out. If the Latched type is selected,
the output relay will stay energized, after the element dropout, and will be de-energized
upon the reset command.
PATH
:
SETPOINTS > S5 INPUTS/OUTPUTS > OUTPUT RELAYS > RELAY 3(6) AUXILIARY
OUTPUT TYPE
Range: Self Reset, Latched
Default: Self Reset
Figure 50: Auxiliary relays
From
Protection
Feature
OR
From
Control
Feature
From
Maintenance
Feature
assigned
aux
.
outputs
:
AND
Relay
(
Ready
=
1
)
SETPOINT
RELA
Y
(3-
6
)
AUXILIAR
Y
OUTPUT
TYPE
Latched
Self-
Reset
AND
AND
OR
AND
OR
RESET
(Relay
Keypad)
RESET
(Communications)
RESET
(Input)
Breaker
Control
OR
Operate
Aux
Output
Relay
(3
-
6
)
Message
&
Event
Recorder
898777.cdr