manualshive.com logo in svg
background image

17

SECTION 7. TESTING AND TROUBLE-

SHOOTING

WARNING:

 Do not change taps on the current sen-

sors or adjust the trip unit settings while the
breaker is carrying current. Failure to adhere to
these instructions will void all warranties.

Testing

1.

Verify that the trip unit is securely installed by

performing a continuity test on the CT wiring and

the trip unit.

a.

Disconnect the black CT wires at each phase

sensor.

b.

Check for continuity with a continuity tester or

VOM from the white lead of the phase A CT to

the white lead of the phase B CT.

c.

Repeat this continuity test for the white leads

of the phase A and phase C CTs.

d.

Measure the resistance across each phase

sensor and compare the values measured to

the values listed in Table 1.

e.

Reconnect the black CT leads to all of the

phase sensors. Ensure that this is done before

continuing with performance testing of the

breaker.

CAUTION:

 In addition to the continuity test

described in Step 1 and before performance testing
of the converted breaker, each phase of the breaker
should be primary injected with a current level of
about 10%, but no more than 20%, of the CT rating.
During the application of test current, activate the
trip unit screen by depressing the battery button on
the trip unit face and check that the test current is
displayed on the screen for each phase tested. If the
trip unit fails to display the test current, stop the
test immediately and verify the installation of the
trip unit and wire harness before proceeding with
any additional testing.

WARNING:

 If the converted breaker is energized or

tested by primary injection with a sufficiently high
test current with a loose or open circuit between the
CTs and the trip unit, damage will occur to the trip
unit, wire harness, 36-pin trip unit connector, and
CTs. Failure to adhere to these instructions will void
all warranties.

2.

Check the insulation on the primary circuit with a

1,000-volt Meggar.

3.

Measure the resistance across the line and load

terminals for each phase using a micro-ohmme-

ter or millivolt tester. If the resistance differs

considerably from phase to phase, the electrical

connections may not be properly tightened or it

could also indicate improper contact wipe.

4.

To verify that the breaker has been properly

retrofitted, perform a primary injection test on

each phase. This test will check the CTs, bus,

wiring harness, flux shifter, and trip unit as a

complete system.

a.

A high-current, low-voltage power supply

should be connected across each line and load

terminal to simulate an overcurrent fault.

b.

Set the long-time trip at 0.5 to minimize the

breaker stress.

c.

When ground fault is installed, the test can be

performed by wiring two adjacent poles in

series or by using the GE Digital Test Kit, cat.

no. TVRMS2. This will prevent the breaker

from tripping because of an unbalanced cur-

rent flow.

CAUTION:

 Do not attempt to use GE Test Kit cat.

no. TVTS1 or TVRMS on this trip unit.

Trouble-Shooting

When malfunctioning is suspected, first examine the
breaker and its power system for abnormal condi-
tions such as the following:

• The breaker is not tripping in response to over-

current conditions or incipient ground faults.

• The breaker is remaining in a trip-free state

because of mechanical interference along its trip

shaft.

• The shunt trip (if present) is activating improp-

erly.

Nuisance Tripping on Ground Fault-Equipped

Breakers

When nuisance tripping occurs on breakers equipped
with ground fault trip, a probable cause is the
existence of a false ground signal. Each phase sensor
is connected to summing circuitry in the trip unit.
Under no-fault conditions on three-wire load circuits,
the currents add to zero and no ground signal is
developed. This current sum is zero only if all three
sensors have the same electrical characteristics. If
one sensor differs from the others (such as by a
different rating or wrong tap setting), the circuitry
can produce an output sufficient to trip the breaker.
Similarly, a discontinuity between any sensor and
the trip unit can cause a false trip signal.
The sensors and their connections should be closely
examined if nuisance tripping is encountered on any
breaker whose MicroVersaTrip Plus or MicroVersa-
Trip PM trip unit has previously demonstrated satis-
factory performance. After disconnecting the breaker

Содержание MicroVersaTrip Plus

Страница 1: ...to ANSI Standard C37 59 allowing the retrofitter to properly install the kit and acceptance test the breaker This publication covers installation of MicroVersaTrip Plus and MicroVersaTrip PM Con versi...

Страница 2: ...Screw Adjustment 8 Microswitch Linkage 8 Flux Shifter Test 8 Installing the Trip Unit Wiring Harness 10 Installing the Trip Unit Mounting Plate 12 Installing the Current Sensors 13 LA 800 Current Sens...

Страница 3: ...pin trip unit connector 10 10 36 pin connector adapter bracket 10 11 Adapter bracket locking tabs 10 12 Installing the push nuts onto the guide pins 11 13 Locking tabs on mounting plate 11 14 Trip uni...

Страница 4: ...ng to the breaker both primary and secondary Remove the breaker to a clean well lighted work area WARNING Low voltage power circuit breakers use high speed stored energy spring operating mecha nisms T...

Страница 5: ...rated in Figure 1 4 Remove the wires from the original current sen sors CTs if present and slide off the CTs 5 Unscrew the knob on the end of the manual charging handle and pull the handle down part w...

Страница 6: ...n of the Micro VersaTrip Plus or MicroVersaTrip PM conversion kit The components provided with the kit are shown in Figure 3 Figure 3 Components supplied with the conversion kit Trip Unit Flux Shifter...

Страница 7: ...nt with the breaker reset link 12 4 Install the flux shifter assembly on the right side of the breaker frame where the original flux shifter if present was removed The two mount ing studs should fit t...

Страница 8: ...and the self locking nut on the bolt Do not overtighten the nut as the bolt must be free to rotate within the connecting links 2 With the breaker in the OPEN reset position push the lower link 7 down...

Страница 9: ...9 Figure 8 Parts sequence for connecting the microswitch link Washers Microswitch Link Breaker Reset Link Flux Shifter Reset Arm 1 4 20 Bolt Self Locking Nut Adjusting Nuts...

Страница 10: ...converted breaker is energized or primary injected with the mounting plate not installed or installed improperly damage will result to the trip unit wire harness 36 pin connector and current sensors...

Страница 11: ...il the assembly is held firmly against the trip unit mounting plate 5 While holding the adapter bracket and connector assembly firmly in place against the mounting plate bend the two locking tabs on t...

Страница 12: ...onnector from the flux shifter 4 Pass the current sensor leads through the hole on the lower left side from the rear of the breaker as shown in Figures 16 and 17 5 If the trip unit is to be connected...

Страница 13: ...3 Reattach the primary disconnect assemblies to all the studs if the breaker is unfused or to only the load lower studs if the breaker is fused 4 If the breaker is fused reinstall the fuse assem blies...

Страница 14: ...nt door SECTION 5 INSTALLING THE TRIP UNIT Use the following procedure to install the trip unit 1 Pull out the locking lever on the trip unit mount ing plate until it snaps into the open position as s...

Страница 15: ...ipment Figures 20 and 21 show the sensor outlines for the 800 A and 1600 A frame sizes respectively 2 Connect the neutral sensor wire harness to the correct taps on the sensor To maintain the same pol...

Страница 16: ...16 Figure 21 Neutral sensor outline for LA 1600 breakers...

Страница 17: ...the resistance differs considerably from phase to phase the electrical connections may not be properly tightened or it could also indicate improper contact wipe 4 To verify that the breaker has been p...

Страница 18: ...t mounted secondary discon nect block Also check for continuity from the breaker mounted neutral secondary discon nect block through to the trip unit wiring har ness connector c If the breaker s lower...

Страница 19: ...19 Figure 22 Cabling diagram for MicroVersaTrip Plus and MicroVersaTrip PM trip units with ground fault on four wire loads...

Страница 20: ...installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be ref...

Отзывы: