PlusTM and
PM™
Units
1.
Introduction
CAIJTION
1M:P0fti ANT INSTRUCTIONS TO ENSOR!
N'IOPE'R Pf'lOOI'lAMMEI'l F\JNCT10N
Figure
3.
Rear view of Micro Versa Trip PM Trip Unit (series
RMS9C).
Figure
4.
Rear view of Micro Versa Trip PM Trip Unit (series
RMS9D).
2
CAUTION:
Removal of a Trip Unit from its breaker
must be performed with the breaker in the OPEN or
TRIPPED position. Draw-out breakers should be
racked out first.
AITENTION:
Pour retirer declencheur , le
disjoncteur doit etre en position ouverte ou
declenchee. Les disjoncteurs debrochables doivent
etre en position debrochee.
CAUTION:
Do not attempt to operate the breaker
without its assigned Trip Unit. Installation of an
incorrect Trip Unit may result in unsafe operation of
the breaker.
AITENTION:
Ne pas utiliser le disjoncteur sans son
declencheur . Une mauvaise installation du
declencheur peut etre dangereuse.
CAUTION:
Removal of the rating plug while the
breaker is carrying current reduces the breaker's
current-carrying capacity to approximately 25% of
�·
the current sensor rating. This may result in unde
sired tripping.
AITENTION:
Si le calibreur est retire alors que le
disjoncteur est sous tension, le declencheur se regle
automatiquement
a
approximativement 25% du
calibre du transformateur de courant. Ceci peut
en trainer un declenchement indesirable.
NOTE:
Trip Units as received may have settings that
are undesirable for the specific application. Ensure
that settings are appropriately adjusted before ener
gizing.
NOTE:
Les disjoncteurs sont livres avec des reglages
standards qui peuvent etre inadequates pour
certaines applications. Verifier ces reglages avant de
mettre le disjoncteur sous tension.