GE MiCOM P40 Agile P14D Скачать руководство пользователя страница 4

Version History

P40 Agile P14D, P14N, P94V

4

P40Agile-VH-EN-9

Major Minor

Relay type: Agile P14N, P14D and P94V

Software 

Version

Hardware 

Suffix

Original Date of 

Issue

Description of Changes

Technical Documentation

50

L

A

April-2017

Permanent ethernet communication loss in P40 Agile relays
Maintenance Record Generated Everytime Gateway is configured in DNP configuration
CS1 and CS2 does not work independently whey CB Comp enabled for CS2

51

A

A

Sep-13

· Ethernet Enhancements for the P94V
· New model P14DA
· Neutral Admittance Protection for the P14DL and P14DZ
· Selectable Measured/Derived NVD.

Undervoltage programmable curve not using standard template used by other Px4x relays

The map of IEC 61850 data model for P34x has errors in Function

With e-terra scada system, the P40 Agile data model extraction stops at Measurments/PriFouMMXU1$CF

When using SBOns control model for the data 'Control/XCBR1$CO$Lock' and both Check Conditions are set the 

Agile relay is dropping the connection to the client.

DNP ALSTOM rebranding in dnpev_devattr.h

QNX kernel can delay user threads for up to 10ms.

Unextracted events are lost on RP1, following relay reboot, using a DNPOE build.

Incorrect response to Object 2 Variation 3 request for Binary Input Event with Relative Time

ISEF, IEF and anything related are not scaled properly when the CT ratio is 5A. 

IEEE Floats are wrong at modbus interface. 

Ethernet application (IE DNP3oe) crashes if a Courier tunnel is continuously opened/closed (as done by 

S1 Agile Measurements viewer).

P14D-TM-EN-1
P14N-TM-EN-1
P94V-TM-EN-1

51

B

A

Nov-13

EF directional function fail to trip

The VCO Status, cell [3582], for the Voltage Controlled Overcurrent isn't updated after a change. The change 

takes effect after a power cycle or change to  V Dep

Object 0 variations: 219, 222, 245 & 247 are incorrect.

P14D-TM-EN-1
P14N-TM-EN-1
P94V-TM-EN-1

51

C

A

June-14

ZR0006 FCT fails; High current drain to opto transformer drive circuit
· Chinese HMI Added
· The DDB 1599-1798 display ”PSL internal 001-200“, but DDB 923-1022 still display "PSL internal 001- 100". Have 
duplicate content.

The VCO Status isn't updated after a change. The edited change does take effect after a power-cycle or a change 

to "V Dep OC V<1 Set" cell 3583.

Object 0 variations: 219, 222, 245 and 247 are incorrect.

52

B

A

P14D-TM-EN-1
P14N-TM-EN-1
P94V-TM-EN-1

Nov-13

Содержание MiCOM P40 Agile P14D

Страница 1: ...GE Energy Connections Grid Solutions MiCOM P40 Agile P14D P14N P94V Version History Feeder Management IED Hardware version A Software version Up to 61 Publication reference P40Agile VH EN 9 ...

Страница 2: ......

Страница 3: ...ion CB Fail trip may fail to operate under faults with DC transient offsets IEC 61850 Client disassociation while reading PloGGIO1 CO block in P14D IEDs IEC61850 Measurements negative values rounding error Agile latch reset when setting group is changed What to do with Pending Reports when BufTm 0 Ed1 Undervoltage programmable curve not using standard template used by other Px4x relays The VCO Sta...

Страница 4: ...er threads for up to 10ms Unextracted events are lost on RP1 following relay reboot using a DNPOE build Incorrect response to Object 2 Variation 3 request for Binary Input Event with Relative Time ISEF IEF and anything related are not scaled properly when the CT ratio is 5A IEEE Floats are wrong at modbus interface Ethernet application IEC61850 DNP3oe crashes if a Courier tunnel is continuously op...

Страница 5: ...elay is set to primary in S1 53 D A Aug 2015 Very sharp pick current level lead relay tripping on IREF 53 E A April 2017 IEC 61850 Connection Disconnection issues DNP3oE Versions Courier Tunnelling doesnot work DNPOE after operated some DI and AI events at the same time the relay Ethernet board seems locked and after a while the relay reboot DNP Over Ethernet Application Crash after many days of P...

Страница 6: ...urst Count HiF Detection FA Steady Fault Incorrect Assertion HIF CHA Hysteresis is not correctly set HIF Burst Threshold is not reset after the adaptive threshold is disabled Maintenance Record Generated Everytime Gateway is configured in DNP configuration 55 A A November 15 CS1 and CS2 does not work independently whey CB Comp enabled for CS2 To retrofit legacy products KAVR100 KAVS and KVTR Pin t...

Страница 7: ...Fault Record after relay reboot P145 Underfrequency issue in Russia SecRmsMMXU1 showing values in primary not secondary IEC 61850 incorrect Courier cell mapping to TotWh and TotVArh in MMTR LNs CB Fail trip may fail to operate under faults with DC transient offsets FUNCTION KEYS column is visible for 20TE devices in P14 Agile data model Default GOOSE Min Cycle Time is wrong Visibility of setting I...

Страница 8: ...ok Feel Start Elements Trip Elements available options Fault Record spread sheet need update Data Group Modbus missing Modbus Number of steps shift from cell 420D V 3 Function to 4211 V 3 Poledead Inh in Look Feel Max value 10Hz could not be set to cells f Df Dt x Dfreq x 1 to 9 via Modbus protocol The mapping Measurements SecMSTA1 MX AvVAr3 mag f was wrong it should map to the cell 0342 3Ph VAr F...

Страница 9: ...P redundancy new hardware boards PCCN Electre features CEI 0 16 2nd round DNP3 memory leak correction AGPL 49 P14D TM EN 7 P14N TM EN 7 P94V TM EN 7 The values of DDBs 1717 1720 read via IEC61850 can not be updated after downloading the new PSL The fault record can t be extracted via CS103 protocol if the previous fault record terminated by Reset CU DNP Over Ethernet Application Crash after many d...

Страница 10: ... events are read as test mode via CS103 protocol No events read from CS103 protocol for DDB 441 Test Mode DDB 771 GOOSE IED Absent DDB 780 IP Addr Conflict DDB 1200 Monitor bit 1 to DDB 1207 Monitor bit 8 IED reboot during the Endurance Test Stress Test at 69Hz Agile RSTP is non responsive at 10Mbps Relay contact 1 doesn t persist data on P14DH model after reboot 61 A A April 2017 TEFD new algorit...

Страница 11: ......

Страница 12: ...s document is indicative only No representation or warranty is given or should be relied on that it is complete or correct or will apply to any particular project This will depend on the technical and commercial circumstances It is provided without liability and is subject to change without notice Reproduction use or disclosure to third parties without express written authority is strictly prohibi...

Отзывы: