05-2806A01, Rev. L
MDS iNET Series Reference Manual
51
The transceiver converts MODBUS/TCP requests to either RTU or ASCII serial MODBUS packets and
sends them to the configured serial port. The transceiver waits up to the timeout period for a reply on the
serial port, and if a reply arrives, the transceiver converts the response back to MODBUS/TCP and sends it
to the connected MODBUS/TCP client. More information can be found in Appendix A,
NOTE:
MODBUS is possible on the COM2 port only.
NOTE:
For information on the MDS iNET 900 ENI, which provides expanded gateway and protocol
conversion capabilities not found in the iNET 900 (DF1 to EIP, and MODBUS to MODBUS TCP
conversions), refer to Appendix A,
Data Buffering
Data buffering is always active regardless of the selected mode. When Seamless mode is selected, a buffer
size of 256 bytes is used. When custom mode is selected, the size options are: 16. 32, 64, 128, and 256 bytes.
The Inter-Frame Delay is settable in either Seamless or Custom modes.
Implementing Configuration Changes
There are several configuration parameters for the Serial Gateway found under the
Serial Configuration
Menu
of the Management System. After making changes to the configuration, you must use the menu’s
“Commit Changes” to assert the changes.
If you are connecting EIA-232 serial devices to the transceiver, review these parameters carefully.
Serial Configuration Wizard
The Serial Configuration Wizard available through the
Serial Gateway Configuration Menu
is recommended
for configuration of serial ports. The wizard uses a step-by-step process, will eliminate possible conflicting
settings, and streamline complex configurations.
The wizard can be bypassed by selecting option
B) View Current Settings
and adjusting the individual set-
tings of the appropriate parameter.
2.6.2 Serial Data Port Configuration Menu
The first two menu items present the identical parameter fields for each port with one exception—Flow
Control. This is available only on COM2.
Содержание MDS iNET Series
Страница 12: ...x MDS iNET Series Reference Manual 05 2806A01 Rev L...
Страница 159: ...05 2806A01 Rev L MDS iNET Series Reference Manual 147 Figure A 22 EDS Wizard Completion Screen...
Страница 165: ...05 2806A01 Rev L MDS iNET Series Reference Manual 153 NOTES...
Страница 166: ...154 MDS iNET Series Reference Manual 05 2806A01 Rev L NOTES...
Страница 173: ...GE MDS LLC Rochester NY 14620 General Business 1 585 242 9600 FAX 1 585 242 9620 Web www gemds com 175 Science Parkway...