The RS232 port is a plug-in interface port (9-pin, Sub-D, male) which enables advanced communication
between the UPS and the computer. Use UPS software for unattended operation of workstations, power
quality related data logging, shutdown notification and control, auto-restart, diagnostics, and battery
conservation features.
We strongly recommend to use only original GE Digital Energy software in combination with the RS232
interface port.

Pin #

Function

  1

GND

  2

RXD

  3

TXD

  4

GND

  5

GND

  6

GND

  7

GND

  8

GND

  9

GND

5.1

General

The Match lite UPS is virtually maintenance free: take care of proper environmental conditions and keep
air inlets-outlets free of dust. Please read 2.1.

5.2

Fuses

If the AC input fuse (1) is defect, be sure it is replaced by a compatible fuse from the same make and
type, e.g. ceramic fuse 3.15Amp slow blow, 1000Amp breaking capacity at 250Vac.

5.3

Batteries

5.3.1

General

The service life of the battery is up to 6 years.
As a healthy battery is critical to the UPS, keypad 'ON/TEST' allows a battery test. When the condition of
the battery is critical, a 

'replace battery'

 alarm will be generated (see 3.3). Charge the batteries for at least

10 hours, switch the UPS off and back on, and perform a self-test. If the alarm persists replace the
batteries as soon as possible.

5.3.2

Battery replacement

-

Warning: first read the safety rules in section 1.2.

-

When replacing the batteries, use the same number and voltage(V)/capacity(Ah).

-

Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal
requirements.

-

Never dispose of batteries in a fire: they may explode.

-

Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to
electrolyte, wash immediately with plenty of water.

-

Avoid charging in a sealed container.

-

Never short circuit batteries. When working with batteries, remove watches, rings or other metal
objects, and only use insulated tools.

Battery replacement procedure

1 remove UPS front panel (two screws on bottom side)
2 remove battery cover plate (four screws)
3 pull out battery, disconnect the battery wires
4 connect the new battery (black -, red +); small sparks can occur, this is normal
5 reinstall the new battery, do not pinch or clamp the wires
6 reinstall battery cover plate and UPS front panel.

1

2

7

8

4

9

5

3

6

4  -  Communication

5  -  Maintenance

Содержание Match lite 500

Страница 1: ...factured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com GE Digital Energy Technology for the Digital World ver 4 0 GB Match lite UPS g ...

Страница 2: ...les 2 2 Installation Procedure 3 OPERATION 3 3 1 Start up 3 1 1 Start up mains available 3 1 2 Start up mains not available 3 2 Use Normal Operation 3 2 1 Normal operating conditions 3 2 2 Self test 3 2 3 Switching off 3 3 Use Status and Alarm Indications 3 3 1 Charger on 3 3 2 Normal operation 3 3 3 On battery 3 3 4 Battery low 3 3 5 Replace battery 3 3 6 Overload 3 3 7 Shutdown 4 COMMUNICATION 6...

Страница 3: ...nect the unit to a wall outlet for a period of approx 48 hours minimum every 3 months The shipping box contains a Match lite UPS a power cord a computer interface cable and this manual After unpacking inspect the UPS for damage If you find any damage please immediately notify the carrier and place of purchase IMPORTANT Before making any connection and switching on the Match lite UPS please check t...

Страница 4: ...2 seconds LED LINE already blinking will illuminate continuously now 2 The equipment connected to the UPS can now be switched on 3 1 2 Start up mains not available If the mains input is absent power cord not connected or mains failure 1 Press keypad ON TEST for 4 seconds until LED BAT illuminates The UPS operates on battery it discharges the batteries 3 2 Use Normal Operation 3 2 1 Normal operatio...

Страница 5: ...mmediate action should be taken Situation LINE BAT buzzer o Charger on 3 3 1 1x s o Normal operation 3 3 2 On battery 3 3 3 1x 4s Battery low 3 3 4 1x s 1x s Replace battery 3 3 5 1x 30s 1x 30s Overload 3 3 6 o Shutdown 3 3 7 1x s Operating modes and corresponding indications see 3 3 1 3 3 7 intermitting continuous resetable press button ON TEST briefly Only the current alarm is muted a next alarm...

Страница 6: ...hutdown of your computer equipment should be completed within 1 minute 3 3 5 Replace battery The battery is bad Perform the self test again to confirm the replace battery condition The alarm only goes out after the next self test if the battery has either been sufficiently charged discharged battery or replaced by a new one worn out battery See also 5 3 3 3 6 Overload The demanded power of the equ...

Страница 7: ...hen the condition of the battery is critical a replace battery alarm will be generated see 3 3 Charge the batteries for at least 10 hours switch the UPS off and back on and perform a self test If the alarm persists replace the batteries as soon as possible 5 3 2 Battery replacement Warning first read the safety rules in section 1 2 When replacing the batteries use the same number and voltage V cap...

Страница 8: ...blinks UPS is in programmed shutdown mode Normal situation UPS will not switch on nor off Computer interface problem Disconnect interface If this solves the problem check interface cable and attached computer UPS will not switch on LEDs LINE and BAT blink Software configuration error Disconnect mains press OFF during 2 seconds to reset the internal processor Blown input fuse See above UPS operates...

Страница 9: ...e of battery start last detected frequency off factory 50 Hz Output frequency stability 0 1Hz battery operation Output waveform step sine wave Power factor 0 6 0 7 at 90 load Transfer time typical 4 ms max 10 ms Buck Boost voltage regulation at 165 275 V input voltage output voltage 190 254V Batteries ratings given for 25 C Nominal voltage Vdc 12 Number x capacity Ah of batteries 1x7 Type 12V seal...

Отзывы: