background image

© 2016 General Electric Company. All rights reserved.

10 

=

GE Oil & Gas

10. Right-click on the 

HART Modem 

and do one of the following:

Selecting 

Network > Rebuild Network

.

or

Selecting 

Find New Devices

.

or

Clicking 

Add New Device, 

Figure 6 appears, highlighting 

SVI II AP HART 5

,

 6

 or 

7

 and 

clicking 

OK

.

Figure 6 Add New Device

11. Right-click on the SVI II AP in the 

Project

 pane and click 

Connect

.

12. Click 

OK

 to the DTM evaluation period warning, if it appears. The SVI II AP DTM opens. 

If the SVI II AP DTM doesn’t open automatically: Select the SVI II AP device you added, 
right-click and select 

Online Parameter

.

Содержание Masoneilan SVI II AP

Страница 1: ...GE Oil Gas Masoneilan SVI II AP Advanced Performance Digital Positioner Bench Quick Start Rev C Instruction Manual GE Data Classification Public ...

Страница 2: ...S AND REGULATIONS APPLICABLE AT THE SITE AND THE PARTICULAR REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION OPERATION OR MAINTENANCE SHOULD FURTHER INFORMATION BE DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT...

Страница 3: ...when to run signatures and produce associated reports This procedure uses GE s ValVue 3 software ver 3 20 or later and the SVI II AP DTM ver 2 10 1 or later This procedure consists of the following major steps 1 Physical Setup on page 4 2 Software Install and Configuration on page 6 3 Perform Setup Wizard on page 11 4 Save Settings and Device Baseline on page 13 Changing the Application to Normal ...

Страница 4: ...lugged If it does not the VIATOR installation includes a utility called USB View for viewing USB connections For a serial connection you can check using Windows Device Manager 3 Prepare the HART hardware by a Plugging the HART Loop Power Calibrator power supply in and setting up the calibrator as per its manual ensuring the mode is correct to supply a 4 20 mA b Plugging the USB plug or serial conn...

Страница 5: ...ore supply pressure than required by the actuator maximum spring pressure Supply pressure for single acting SVI II AP and AP High Flow 20 100 psi 1 4 6 9 bar 138 690 kPa Supply pressure for double acting SVI II AP 25 150 psi 1 73 10 3 bar 172 1030 kPa Minimum tubing diameter 1 4 6 mm x 4 mm Any other pneumatic accessories are correctly piped without restricting the SVI II AP output s to the actuat...

Страница 6: ...nload the SVI II AP DTM and ValVue 3 and install See Masoneilan Software on page 14 for download site 2 Download the Codewrights HART Communication DTM and install See Codewrights HART Communication DTM on page 16 for download site 3 Sign on to ValVue 3 with default values User name admin Password ValVue 3 ...

Страница 7: ... ValVue and the SVI II AP DTM You then have an additional 30 day period with just standard features after which you must register to continue using the product We strongly encourage you to register your license with us as soon as possible Contact GE at software reg ge com The evaluation periods for both are independent of each other and commence with first use If you have updated ValVue a dialog a...

Страница 8: ...e 2 appears Figure 2 DTM Library Management Before Update 5 Click Update and once the DTM Updates list refreshes select the HART Communications and the SVI II AP HART 5 HART 6 or HART 7 Figure 3 DTM Library Management After Update 6 Click Add Sel and then click OK to close DTM Library Management dialog ...

Страница 9: ...rs Select HART Modem and click OK Figure 4 Add Field Network 8 Click OK again to add the HART Modem to Network View and Figure 5 appears Figure 5 HART Modem Configuration Tab 9 Ensure the Serial Interface pulldown and the Address scan fields are correct Click Apply and then OK If device is connected or powered through DCS set Master to Secondary Master NOTE ...

Страница 10: ...cking Add New Device Figure 6 appears highlighting SVI II AP HART 5 6 or 7 and clicking OK Figure 6 Add New Device 11 Right click on the SVI II AP in the Project pane and click Connect 12 Click OK to the DTM evaluation period warning if it appears The SVI II AP DTM opens If the SVI II AP DTM doesn t open automatically Select the SVI II AP device you added right click and select Online Parameter ...

Страница 11: ...Masoneilan SVI II AP Bench Quick Start Manual 11 2016 General Electric Company All rights reserved 13 Check that the SVI II AP is connected see red oval in Figure 7 Figure 7 Connected ...

Страница 12: ...ditional Functions Communication and Figure 8 appears Correct the Polling Address and click Apply Disconnect and then reconnect Figure 8 Communication Tab 14 Click Upload All Parameters icon see red box in Figure 7 Upload means to pull data from the SVI II AP and load data into DTM onto the PC Download puts data from the DTM into the SVI II AP NOTE ...

Страница 13: ...Stops range calibration confirm that the valve is isolated from the process This procedure exhausts and then fills the valve actuator to supply pressure and therefore strokes the valve over its full range Supply pressure MUST NOT exceed the actuator pressure rating marked on the actuator Positioner supply pressure MUST BE at least 5 psi higher than the upper spring range of the valve CAUTION Proce...

Страница 14: ...reserved 14 GE Oil Gas 1 Select the Setup Wizard tab and ensure the mode is in Setup Figure 9 Setup Wizard Tab 2 Configure the fields on each tab as required and click to move to the next tab 3 Navigate through to the Device Mode step and click ...

Страница 15: ... information by a Right clicking the AP device in the Project pane and select Additional Functions Report and the report appears Figure 10 Example Report b Clicking the Disconnect icon on the ValVue 3 toolbar c Clicking Network Exit to close the DTM If you have unsaved data click the Download Parameters to Device icon to save 3 Connect the AP wires to next item on order Click Find New Devices Go t...

Страница 16: ...dix A Download Instructions Masoneilan Software 1 Go to the Download Center http www ge mcs com en download html make selections as shown Figure 11 and click Search Figure 11 Download Center Search for Valve 3 The results appear Figure 12 Figure 12 Search Results ValVue 3 ...

Страница 17: ...ric Company All rights reserved Figure 13 Download Center Search for SVI II AP DTM 2 Scroll down to find the specific software program of choice SVI II AP DTM or ValVue 3 Click the blue link to download 3 Click I Accept for the terms Figure 14 Figure 14 Software Terms ...

Страница 18: ...nstall from the website Codewrights HART Communication DTM You must download and install this DTM to use Masoneilan s HART based DTM Go to the link http www codewrights biz index php en downloads software and follow instructions to download and install the CW_CommDTM_HART Filling in this form registers the download It does not register the software Download install and follow registration instruct...

Страница 19: ......

Страница 20: ...8666 Fax 88 31 18 1641438 Skelmersdale Phone 44 1695 526 00 Fax 44 1695 526 01 FRANCE Courbevoie Phone 33 1 4904 9000 Fax 88 33 1 4904 9010 RUSSIA Veliky Novgorod Phone 7 8162 55 7898 Fax 88 7 8162 55 7921 UNITED STATES Massachusetts Phone 1 508 586 4600 Fax 88 1 508 427 8971 GERMANY Ratingen Phone 49 2102 108 0 Fax 88 49 2102 108 111 Moscow Phone 7 495 585 1276 Fax 88 7 495 585 1279 Corpus Christ...

Отзывы: