Step 2: Set Tag and Address
Using NI Configurator:
1. Import DD/CFF files.
2. Right-click on the device, select
Set Tag
, follow the prompts to enter a
Tag.
3. Click
Set
.
4. Right-click on the device, select
Set Address,
follow the prompts to enter an
Address.
5. Click
Set
.
Do not navigate to the NI DD folder and copy the
DD file onto itself.
Do not deactivate the Set to OOS mode checkbox.
The block must be in OOS to change the Tag.
If the device is at the temporary address range (248
(0xF8)- 251 (OxFB)), you must set the address
outside of that range.
Do not deactivate the Set to OOS mode checkbox.
The block must be in OOS to change the Address.