Masoneilan SVi1000 Bench Quick Start Manual
=
|
5
© 2016 General Electric Company. All rights reserved.
5. Pipe the SVi1000 to the actuator. Ensure:
The airset provides the SVi1000 with at least 5-10 psig more supply pressure than
required by the actuator (maximum spring pressure). Supply pressure:
15 -100 psi (1.03 - 7 bar) (103 - 690 kPa)
Minimum tubing diameter 1
⁄
4" (6mm x 4mm)
Any other pneumatic accessories are correctly piped without restricting the SVi1000
output(s) to the actuator.
2. Software Install and Configuration
1. Download the SVi1000 DTM and ValVue 3 and install. See “Masoneilan Software” on
page 14 for download site.
2. Download the Codewrights HART
®
Communication DTM and install. See “Codewrights
HART® Communication DTM” on page 15 for download site.
3. Sign on to ValVue 3 with default values:
User name
admin
.
Password
ValVue 3
.
For security purposes, you are forced to change your password
during the first use.
GE recommends registering your software immediately. You are
required to register after a 30 day trial period. After the trial period
you won’t be able to use the software until you complete the
registration process that the software guides you through.
If you have updated ValVue, a dialog appears when you open ValVue 3:
Click:
Yes
and the library is updated.
No
and you need to manually updated from the DTM Library Management dia-
log to access any new functionality.
ValVue version 3.30 or later. For earlier versions continue with manual DTM
Library update.
NOTE
NOTE