CHAPTER 3: INSTALLATION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
3–17
FIGURE 3–18: Summation Method with Phase CTs
FIGURE 3–19: Summation Method without Phase CTs (Phase CTs wiring is shown in Figure 3-12)
3.2.5
Voltage Inputs
The 469 has three channels for AC voltage inputs, each with an isolating transformer. There
are no internal fuses or ground connections on the voltage inputs. The maximum VT ratio is
300.00:1. The two VT connections are open delta (see FIGURE 3–12:
on page 3–11) or wye (see below). The voltage channels are connected in wye internally,
which means that the jumper shown on the delta-source connection of the typical wiring
diagram, between the phase B input and the 469 neutral terminal, must be installed for
open delta VTs.
C
B
A
COM
GROUND
CURRENT INPUTS
PHASE C
1A/5A
1A/5A COM
PHASE A
COM
1A/5A
PHASE B
1A/5A
GROUND
COM
COM
DIFFERENTIAL INPUTS
PHASE A
COM
1A/5A
COM
1A/5A
PHASE B
806846A3.DWG
COM
1A/5A
PHASE C
H10
G8
G6
H6
G7
H7
H8
G9
H9
G10
PHASE C CT
PHASE A CT
PHASE B CT
MOTOR
H3
G3
G4
H4
G5
H5
PHASE B CT
DIFF.
PHASE A CT
PHASE C CT
DIFF.
DIFF.
50:.025
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...