CHAPTER 2: INTRODUCTION
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–15
PRODUCTION TESTS
Thermal cycling: ............................................Operational test at ambient, reducing to –40°C and then
increasing to 60°C
Dielectric strength: .......................................(order code ’LO’) 550 VAC for 1 second
(order code ’HI’) 2200 VAC for 1 second
DO NOT CONNECT FILTER GROUND TO SAFETY GROUND DURING ANY PRODUCTION
TESTS!
2.2.10 Certification
CERTIFICATION
ACA:.......................................................................conforms to RF emissions for Australia, tick mark
CE:..........................................................................conforms to EN 55011/CISPR 11, EN 50082-2
EN: .........................................................................EN50263 EMC - CE for Europe
FCC:.......................................................................conforms to RF emissions for North America, part 15
IEC:.........................................................................conforms to 1010-1, LVD - CE for Europe
ISO:........................................................................Manufactured under an ISO9001 registered system.
UL:..........................................................................UL listed E83849 for the USA and Canada
IEC 60068-2-38
Composite Temperature/Humidity
65/–10°C at 93% RH
IEC 60255-5
Dielectric Strength
2300 V AC
IEC 60255-5
Impulse Voltage
5 kV
IEC 60255-5
Insulation Resistance
>100 M
Ω
/ 500 V AC / 10 s
IEC 60255-21-1
Sinusoidal Vibration
2 g
IEC 60255-22-1
Damped Oscillatory Burst, 1 MHz
2.5 kV / 1 kV
IEC 60255-22-2
Electrostatic Discharge: Direct
8 kV
IEC 60255-22-3
Radiated RF Immunity
10 V/m
IEC 60255-22-4
Electrical Fast Transient / Burst Immunity
4 kV
IEC 60255-22-5
Surge Immunity
4 kV / 2 kV
IEC 60255-22-6
Conducted RF Immunity, 150 kHz to 80 MHz
10 V/m
IEC 60255-25
Radiated RF Emission
Group 1 Class A
IEC 60255-25
Conducted RF Emission
Group 1 Class A
IEC 60529
Ingress of Solid Objects and Water (IP)
IP40 (front), IP20 (back)
IEC 61000-4-11
Voltage Dip; Voltage Interruption
0%, 40%, 100%
IEEE C37.90.1
Fast Transient SWC
±4 kV
IEEE C37.90.1
Oscillatory Transient SWC
±2.5 kV
IEEE C37.90.3
Electrostatic Discharge: Air and Direct
15 kV / 8 kV
Standard
Test Name
Level
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...