CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–105
5.14.6 Comm Port Monitor
PATH: SETTINGS
S13 469 TESTING
COMMUNICATION PORT MONITOR
During the course of troubleshooting communications problems, it can be very useful to
see the data that is first being transmitted to the 469 from some master device, and then
see the data that the 469 transmits back to that master device. The messages shown here
should make it possible to view that data. Any of the three communications ports may be
monitored. After the communication buffers have been cleared, any data received from
the communications port being monitored will be stored in the Rx1 and Rx2 buffers with ‘//
’ acting as a character break between messages. If the 469 transmits a message, it will
appear in the Tx1 and Tx2 buffers. In addition to these buffers, there is a message that will
indicate the status of the last received message.
5.14.7 GR Multilin Use Only
PATH: SETTINGS
S13 469 TESTING
GE MULTILIN USE ONLY
This section is for use by GE Grid Solutions personnel for testing and calibration purposes.
COMMUNICATION
[
]
PORT MONITOR
MONITOR COMM. PORT:
Computer RS485
Range: Computer RS485, Auxiliary
RS485, Front Panel RS232
MESSAGE
CLEAR COMM.
BUFFERS: No
Range: No, Yes
MESSAGE
LAST Rx BUFFER:
Received OK
Range: Buffer Cleared, Received OK,
Wrong Slave Addr., Illegal
Function, Illegal Count, Illegal
Reg. Addr., CRC Error, Illegal
Data
MESSAGE
Rx1: 02,03,00,67,00,
03,B4,27,//----------
Range: received data in HEX
MESSAGE
Rx2: ----------------
---------------------
Range: received data in HEX
MESSAGE
Tx1: 02,03,06,00,64,
00,0A,00,0F//--------
Range: transmitted data in HEX
MESSAGE
Tx2: ----------------
---------------------
Range: transmitted data in HEX
GE MULTILIN
[
]
USE ONLY
GE MULTILIN USE ONLY
CODE: 0
Range: N/A
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...