CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–99
For example, two motors on a dual motor drive are each protected a 469. The motors
should be at the same power level (kW). Connect the analog outputs (programmed for kW)
from both relays to the analog inputs of one relay. Program the analog input differential to
monitor the two motors kW and trip at a predetermined level.
5.13.4 Analog Input Diff 3-4
PATH: SETTINGS
S12 ANALOG I/O
ANALOG INPUT DIFF 3–4
NOTE
Note
This settings menu is seen only if Analog Inputs 3 and 4 are enabled. The
ANALOG IN DIFF 3-
4 TRIP LEVEL
and
ANALOG IN DIFF 3-4 ALARM LEVEL
settings are shown units of “%” if the
ANALOG IN DIFF 3-4 COMPARISON
is “%Diff” or in units defined by the
ANALOG INPUT 3 UNITS
settings if
ANALOG IN DIFF 3-4 COMPARISON
is “Abs Diff”.
ANALOG INPUT
[
]
DIFF 3-4
ANALOG IN DIFF 3-4:
Disabled
Range: Disabled, Enabled
MESSAGE
ANALOG IN DIFF 3-4
NAME: Analog 3-4
Range: 12 alphanumeric characters
MESSAGE
ANALOG IN DIFF 3-4
COMPARISON: % Diff
Range: % Diff, Abs. Diff
MESSAGE
ANALOG IN DIFF 3-4
LOGIC: 3<>4
Range: 3<>4, 3>4, 4>3
MESSAGE
ANALOG IN DIFF 3-4
ACTIVE: Always
Range: Always, Start/Run
MESSAGE
A/I DIFF 3-4 BLOCK
FROM START: 0 s
Range: 0 to 5000 s in steps of 1
MESSAGE
ANALOG IN DIFF 3-4
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
ANALOG IN DIFF 3-4
ALARM LEVEL: 10%
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 3-4
ALARM DELAY: 0.1 s
Range: 0.1 to 300.0 s in steps of 0.1
MESSAGE
ANALOG IN DIFF 3-4
EVENTS: Off
Range: On, Off
MESSAGE
ANALOG IN DIFF 3-4
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
ANALOG IN DIFF 3-4
TRIP LEVEL: 10%
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 3-4
TRIP DELAY: 0.1 s
Range: 0.1 to 300.0 s in steps of 0.1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...