5–96
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.13.2 Analog Inputs 1 to 4
PATH: SETTINGS
S12 ANALOG I/O
ANALOG INPUT 1(4)
MWhrs
0.000 to 999999.999 MWhrs
0.001
50.000
100.000
Analog In Diff 1-2
–50000 to +50000
1
0
100
Analog In Diff 3-4
–50000 to +50000
1
0
100
Torque
0 to 999999.9
0.1
0
100
Table 5–3: Analog Output Parameter Selection Table
PARAMETER NAME
RANGE / UNITS
STEP
DEFAULT
MIN.
MAX
ANALOG
[
]
INPUT 1
ANALOG INPUT 1:
Disabled
Range: Disabled, 4-20 mA, 0-20 mA, 0-
1 mA
MESSAGE
ANALOG INPUT 1 NAME:
Analog I/P 1
Range: 12 alphanumeric characters
MESSAGE
ANALOG INPUT 1 UNITS:
Units
Range: 6 alphanumeric characters
MESSAGE
ANALOG INPUT 1
MINIMUM: 0
Range: –50000 to 50000 in steps of 1
MESSAGE
ANALOG INPUT 1
MAXIMUM: 100
Range: –50000 to 50000 in steps of 1
MESSAGE
BLOCK ANALOG INPUT 1
FROM START: 0 s
Range: 0 to 5000 s in steps of 1
MESSAGE
ANALOG INPUT 1
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
ANALOG INPUT 1 ALARM
LEVEL: 10 Units
Range: –50000 to 50000 in steps of 1
Units reflect
ANALOG INPUT 1
UNITS
above
MESSAGE
ANALOG INPUT 1 ALARM
PICKUP: Over
Range: Over, Under
MESSAGE
ANALOG INPUT 1 ALARM
DELAY: 0.1 s
Range: 0.1 to 300.0 s in steps of 0.1
MESSAGE
ANALOG INPUT 1 ALARM
EVENTS: Off
Range: On, Off
MESSAGE
ANALOG INPUT 1
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3 Trip & Auxiliary3
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...