RTDs 1 through 6 default to “Stator” RTD type. There are individual alarm and trip
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.
The alarm level is normally set slightly above the normal running temperature. The high
alarm is usually set as a warning of a trip or to initiate an orderly shutdown before tripping
occurs. The trip level is normally set at the insulation rating. Trip voting has been added for
extra reliability in the event of RTD malfunction. If enabled, a second RTD must also exceed
the trip temperature of the RTD being checked before a trip will be issued. If the RTD is
chosen to vote with itself, the voting feature is disabled. Each RTD name may be changed if
desired.
5.9.3
RTDs 7 to 10
PATH: SETTINGS
S8 RTD TEMPERATURE
RTD #7(10)
MESSAGE
RTD #1 TRIP
TEMPERATURE: 155°C
Range: 1 to 250°C in steps of 1
RTD #7
[
]
RTD #7 APPLICATION:
Bearing
Range: Stator, Bearing, Ambient, Other,
None
MESSAGE
RTD #7 NAME:
Range: 8 alphanumeric characters
MESSAGE
RTD #7 ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
RTD #7 ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #7 HIGH ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
HIGH ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
RTD #7 HIGH ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #7 ALARM
EVENTS: Off
Range: On, Off
MESSAGE
RTD #7 TRIP:
Off
Range: Off, Latched, Unlatched
MESSAGE
RTD #7 TRIP VOTING:
RTD #7
Range: RTD #1 to RTD #12
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3, Trip & Auxiliary3
MESSAGE
RTD #7 TRIP
TEMPERATURE: 90°C
Range: 1 to 250°C in steps of 1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...