CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–59
In simple terms, the RTD bias feature is real feedback of the measured stator temperature.
This feedback acts as correction of the thermal model for unforeseen situations. Since
RTDs are relatively slow to respond, RTD biasing is good for correction and slow motor
heating. The rest of the thermal model is required during starting and heavy overload
conditions when motor heating is relatively fast.
Note that the RTD bias feature alone cannot create a trip. If the RTD bias forces thermal
capacity used to 100%, the motor current must be above the overload pickup before an
overload trip occurs. Presumably, the motor would trip on stator RTD temperature at that
time.
FIGURE 5–16: RTD Bias Curve
Maximum Stator RTD Temperature
0
20
40
60
80
100
–50
0
50
100
150
200
250
R
T
D
B
i
as Ma
xi
mum
R
T
D
B
i
as
C
enter Po
i
nt
R
T
D
B
i
as M
i
n
i
mum
Hot/Cold = 0.85
Rated Temperature=130°C
Insulation Rating=155°C
RTD
Thermal
Capacity
Used
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...