8.3.3.2
Keyphasor
Inputs 12-13 support Keyphasor sensors to collect air gap value and shaft rotation speed. In Heavy Duty turbine applications,
a Keyphasor is used to calculate the position and rotating speed of a rotating shaft. Keyphasor algorithms report a conditioned
air gap value and shaft rotation speed.
Attention
YVIBS1B does not support 1 Keyphasor on Input 13. YVIBS1B supports 2
Keyphasors on Inputs 12 and 13.
Keyphasor Input Processing
GAPn_KPH# – The conditioned Position or Gap value in engineering units (EU).
Gap values are filtered through a 2-pole, low-pass filter with a fixed cutoff frequency of 8 Hz. At low speeds (100 RPM with
10% hysteresis), the Gap values bypass the filter, instead using a median selection. This allows for visual inspection of the
Gap signal to show the Keyphasor edge more clearly at low speeds, removing the time delay and distortion associated with
the filter. The output of the gap filter is passed through a rolling average filter prior to scaling. Gap Values are converted from
Volts to EU.
Gap
Filter
Mvg
Avg
Filter
A/B
A
B
V
GAP
V
FILT
Scale(V/EU)
V
KPH
Median
Select
RPM < 100
10% hyst
N
Y
V
MED
A - B
A
EU
GAP
GAPn_KPH#
B
Scale Offset(EU)
GAPn_KPH# Signal Path (Keyphasor)
Scale_Off
is the Scale Offset parameter used to remove the nominal Gap value from the measured Gap value. Units are
engineering units (EU).
SysLim1GAPn, SysLim2GAPn – System Limit status for GAPn_KPH# value as True/False.
RPM_KPH# - The calculated shaft rotation speed in RPM.
Shaft rotation speed is calculated by detecting the time between Keyphasor transitions. Since there is only a single transition
per shaft rotation, shaft rotation speed is computed once per rotation, however this requires two rotations of data for the
computation. This value requires at least two full rotations before it can be computed.
At rotating speeds above 1000 RPM, RPM_KPH# is computed as the average of the speed over 4 rotations. This impacts the
rate at which the RPM_KPH# signal will respond to changes in speed.
Note
Only RPM_KPH1 is used by the Wideband Vibration to perform Scan Filtering.
246
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...