6.7
Power and I/O Field Wiring
6.7.1
General Requirements
•
Maximum length (unless specified) 300 m (984.25 ft)
•
Individual minimum stated wire size is for electrical needs
•
Clamp-type terminals accept two 14 AWG wires or one 12 AWG wire
•
Terminal blocks accept two 12 AWG wires
•
PTs and CTs use 10 AWG stranded wire
Note
Wires with appropriate temperature ratings must be used, especially in applications where the internal cabinet ambient
temperature can exceed 60
°
C (140
°
F).
It is standard practice to use shielded cable with control equipment. Shielding provides the following benefits:
•
Generally, shielding protects a wire or combination of wires from its environment.
•
Low-level signals may require shielding to prevent signal interference due to the capacitive coupling effect between two
sources of potential energy.
6.7.2
I/O Field Wiring Restrictions
Board
Limitation
TBAI
15 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
STAI
15 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
SAII
15 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
TBAO
Driven devices should not exceed a resistance of 900 Ω and can be located up to 300 m (984 ft) from the control cabinet
STAO
Driven devices should not exceed a resistance of 900 Ω and can be located up to 300 m (984 ft) from the control cabinet
PCNO
CANopen cable limits are defined by the standard. GEH-6721_Vol_II provides and a table with baud rate to maximum distances
PFFA
Foundation Fieldbus standards for cabling apply
SHRA
15 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
PPRF
GEH-6721_Vol_II provides a summary of Profibus cable requirements including a bus length vs. data rate table
PRTD
The eight RTDs can be located up to 300 meters (984 feet) from the distributed I/O cabinet with a maximum two-way cable
resistance of 15 Ω
PSCA
GEH-6721_Vol_II lists cable distance and maximum baud rate for the three supported communication standards
PTCC
Thermocouples can be located up to 300 meters (984 feet) from the turbine I/O panel with a maximum two-way cable resistance of
450 Ω
PVIB
Often sensors used with this input module impose their own cabling requirements
PAMC
Often sensors used with this input module impose their own cabling requirements
PCLA
For thermocouples- 450 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
For analog inputs- 15 Ω maximum two-way cable resistance, cable length up to 300 m (984 ft)
Other signals do not list a cable specification so the product level requirement applies
PPRA
RS232 and RS485 standards are invoked for speed repeater output signals
PPRO
V3 383 TPRO and 388 SPRO for voltage sensing limits cable length up to 1,000 ft. of 18 AWG wiring
PSCH
GEH-6721_Vol_II provides cable distance and maximum baud rate for the three supported communication standards
Installation Guidelines
GEH-6721_Vol_I_BP System Guide 149
Public Information
Содержание Mark VIe
Страница 61: ...Example UCSx Controller Label Control System Overview GEH 6721_Vol_I_BP System Guide 61 Public Information ...
Страница 66: ...Notes 66 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 74: ...Notes 74 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 116: ...Notes 116 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 164: ...Notes 164 GEH 6721_Vol_I_BP GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 198: ...Notes 198 GEH 6721_Vol_I Mark VIe and Mark VIeS Control Systems Volume I Public Information ...
Страница 201: ......
Страница 202: ...Public Information ...