6-12
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
METERING
CHAPTER 6: ACTUAL VALUES
6
Total Received Port A
is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B
is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors
is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A
is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B
is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
6.3.22 TxGOOSE status
ACTUAL VALUES
STATUS
TxGOOSE STATUS
This status is relevant to R-GOOSE reception when configured for SSM or ASM reception modes. It is not relevant for GOOSE
or for R-GOOSE in unicast reception mode.
ARP
— The unicast mode of R-GOOSE transmission requires Address Resolution Protocol (ARP) for the resolution of the
network layer address into the MAC layer address. R-TxGOOSE## ARP status On indicates that ARP responses are being
received and the destination MAC address for R-GOOSE transmissions has been obtained. This status remains Off if
TxGOOSE## is not configured for R-GOOSE. It also remains Off if setting R-TxGOOSE1 DST IP is set to a multicast address. In
the case where setting R-TxGOOSE1 DST IP is configured with a unicast address and this status indicates Off, TxGOOSE##
transmission will be off, and therefore communication network diagnosis needs to be carried out.
This status is only applicable for R-GOOSE transmission with setting R-TxGOOSE1 DST IP set to a unicast IP address. It is not
applicable for GOOSE or for R-GOOSE when setting R-TxGOOSE1 DST IP is multicast.
6.4 Metering
6.4.1 Metering conventions
6.4.1.1 UR convention for measuring power and energy
The figure illustrates the conventions established for use in UR devices.
The M60 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
TxGOOSE STATUS
R-TxGOOSE 1
ARP: Off
Range: On, Off
R-TxGOOSE 16
ARP: Off
Range: On, Off
The M60 is provided with optional IEC 61850 capability. This feature is specified as a software option at the
time of ordering. See the Order Codes section of chapter 2 for details.
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...