5-102
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
The M60 can specify a maximum of five clients for its IEC 104 connections. These are IP addresses for the controllers to
which the M60 can connect. A maximum of two simultaneous connections are supported at any given time.
5.3.5.16 EGD protocol
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
EGD PROTOCOL
Ethernet Global Data (EGD) is a suite of protocols used for the real-time transfer of data for display and control purposes.
The relay can be configured to ‘produce’ EGD data exchanges, and other devices can be configured to ‘consume’ EGD data
exchanges. The number of produced exchanges (up to three), the data items in each exchange (up to 50), and the
exchange production rate can be configured.
The relay supports one fast EGD exchange and two slow EGD exchanges. There are 20 data items in the fast-produced
EGD exchange and 50 data items in each slow-produced exchange.
EGD cannot be used to transfer data between UR series relays. The relay supports EGD production only. An EGD exchange
is not be transmitted unless the destination address is non-zero, and at least the first data item address is set to a valid
Modbus register address. The default setting value of “0” is considered invalid.
Fast exchanges (50 to 1000 ms) are generally used in control schemes. The M60 has one fast exchange (exchange 1) and
two slow exchanges (exchange 2 and 3).
The settings menu for the fast EGD exchange follows.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
EGD PROTOCOL
FAST PROD EXCH 1 CONFIGURATION
The settings menu for the slow EGD exchanges follows.
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
EGD PROTOCOL
SLOW PROD EXCH 1(2) CONFIGURATION
EGD PROTOCOL
FAST PROD EXCH 1
CONFIGURATION
See below
SLOW PROD EXCH 1
CONFIGURATION
See below
SLOW PROD EXCH 2
CONFIGURATION
See below
The M60 is provided with optional Ethernet Global Data (EGD) communications capability. This feature is
specified as a software option at the time of ordering. See the Order Codes section in chapter 2 for details.
FAST PROD EXCH 1
CONFIGURATION
EXCH 1 FUNCTION:
Disable
Range: Disable, Enable
EXCH 1 DESTINATION:
0.0.0.0
Range: standard IP address
EXCH 1 DATA RATE:
1000 ms
Range: 50 to 1000 ms in steps of 1
EXCH 1 DATA ITEM 1:
0
Range: 0 to 65535 in steps of 1 (Modbus register
address range)
EXCH 1 DATA ITEM 20:
0
Range: 0 to 65535 in steps of 1 (Modbus register
address range)
SLOW PROD EXCH 1
CONFIGURATION
EXCH 1 FUNCTION:
Disable
Range: Disable, Enable
EXCH 1 DESTINATION:
0.0.0.0
Range: standard IP address
EXCH 1 DATA RATE:
1000 ms
Range: 50 to 1000 ms in steps of 1
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...