
34
Connections for M-PRO 40
Location
Terminal
Function
PAMM
A1
PAMM
A2
OUTPUT 4, normally open volt free contact: Operates when the REF (or SEF) element trips
the ACB. This is used to trip an upstream HV breaker.
PAMM
A3
PAMM
A4
OUTPUT 3, normally open volt free contact: Used to control shunt trip to open the ACB via
serial link.
PAMM
A5
PAMM
A6
OUTPUT 2, normally open volt free contact: Load monitoring output will indicate that pre-trip
warn or load shedding is active.
PAMM
A7
PAMM
A8
OUTPUT 1, normally open volt free contact: Used to control closing coil, facilitating closure
of ACB via serial link.
PAMM
A9
Input 4
PAMM
A10
Input 3
PAMM
A11
Input 2
PAMM
A12
Input 1
PAMM
A13
Input common
PAMM
A14
Remote Rogowski coil – positive
PAMM
A15
Remote Rogowski coil – negative
PAMM
A16
Host serial link – screen connection
PAMM
A17
Host serial link – M-PRO Tx positive
PAMM
A18
Host serial link – M-PRO Tx negative
PAMM
A19
Host serial link – M-PRO Rx positive
PAMM
A20
Host serial link – M-PRO Rx negative
LT ‘B’ block
B3
LT ‘B’ block
B4
Earth leg CT input – non polarised
LT ‘B’ block
B5
Auxiliary power supply input – positive
LT ‘B’ block
B6
Auxiliary power supply input – negative
Connections for M-PRO 30
Location
Terminal
Function
PAMM
A1
PAMM
A2
OUTPUT 4, normally open volt free contact: Operates when the REF (or SEF) element trips
the ACB. This is used to trip an upstream HV breaker.
PAMM
A3
PAMM
A4
OUTPUT 3, normally open volt free contact: Operates when M-Pro has opened the ACB
due to a trip condition.
PAMM
A5
PAMM
A6
OUTPUT 2, normally open volt free contact: Load monitoring output operates if pre-trip
alarm or load shedding limits are exceeded.
PAMM
A7
PAMM
A8
OUTPUT 1, normally closed volt free contact, opens under the following conditions:
Microprocessor malfunction, primary contact maintenance alarm or a digital input is active.
PAMM
A9
Input 4
PAMM
A10
Input 3
PAMM
A11
Input 2
PAMM
A12
Input 1
PAMM
A13
Input common
PAMM
A14
Remote Rogowski coil – positive
PAMM
A15
Remote Rogowski coil – negative
LT ‘B’ block
B3
LT ‘B’ block
B4
Earth leg CT input – non polarised
LT ‘B’ block
B5
Auxiliary power supply input – positive
LT ‘B’ block
B6
Auxiliary power supply input – negative
Connections for M-PRO 20
Location
Terminal
Function
PAMM
A14
Remote Rogowski coil – positive
PAMM
A15
Remote Rogowski coil – negative
LT ‘B’ block
B5
Auxiliary power supply input – positive
LT ‘B’ block
B6
Auxiliary power supply input – negative
Connections for M-PRO 17
Location
Terminal
Function
LT ‘A’ block
A8
Remote Rogowski coil – positive
LT ‘A’ block
A9
Remote Rogowski coil – negative
LT ‘B’ block
B5
Auxiliary power supply input - positive
LT ‘B’ block
B6
Auxiliary power supply input - negative