GE Lumination BL44 Series Скачать руководство пользователя страница 3

Dimming line

(optional)

3

Optional:

 If using a dimmer, connect black and red wires 

of the dimming line to the D1 and D2 positions on the 

terminal block. 

2

1

Fasten mounting brackets over screws but do not 

tighten them at this point. Note that bracket flaps have 

to be aligned with the groove.

Slide two bracket mounting screws into housing groove 

on each side (four screws per housing). If the screw head 

cannot pass through end cover groove, remove end covers 

and slide the screw head directly into the housing groove, 

then re-install end covers.

Luminaire Installation

Follow diagram A for 0-10V or diagram B for DALI. Run wires from controller through a different knockout than the AC input wire. 

At output side of LED Driver, make appropriate connections using twist-on wire connectors. Follow lighting controller installation 

instructions.

BLU/WHT

BLK/WHT

YEL

GRY

VIO

VIO/WHT

LED Driv

er

To 0-10V 

Dimmer

0-10V -

0-10V +

BLU/WHT

BLK/WHT

YEL

GRY

VIO

VIO/WHT

LED Driv

er

To DALI 

Controller

DALI/Prog
DALI/Prog

B

DALI controller wiring diagram

A

0-10V dimmer wiring diagram

Optional Installation:  0-10 Volt Dimming or DALI Lighting Controller

4

Replace cover using at least one star washer under 

countersunk screwhead.

Star washer

Do not 

tighten yet

Содержание Lumination BL44 Series

Страница 1: ...2mm2 Product not IC rated RISQUES DE DÉCHARGES ÉLECTRIQUES Coupez l alimentation avant d inspecter installer ou déplacer le luminaire Assurez vous de correctement mettre à la terre le boîtier d alimentation électrique RISQUES D INCENDIE Respectez tous les codes IEC et codes locaux N utilisez que des fils approuvés par UL ou IEC pour les entrées sorties de connexion Taille minimum 18 AWG 0 82mm2 Le...

Страница 2: ...r work gloves to prevent dirt and oil from being transferred to the luminaire Electrical Connections Dimming line optional AC line AC line 2 1 Connect the green wire of the AC line to the middle position on the terminal block Connect brown or black line wire to the L1 position and the blue neutral wire to the N position Loosen cable gland nuts to insert AC line Optionally insert dimming line into ...

Страница 3: ...n re install end covers Luminaire Installation Follow diagram A for 0 10V or diagram B for DALI Run wires from controller through a different knockout than the AC input wire At output side of LED Driver make appropriate connections using twist on wire connectors Follow lighting controller installation instructions BLU WHT BLK WHT YEL GRY VIO VIO WHT LED Driver To 0 10V Dimmer 0 10V 0 10V BLU WHT B...

Страница 4: ...emarks of the General Electric Company 2012 GE Lighting Solutions LLC Information provided is subject to change without notice All values are design or typical values when measured under laboratory conditions Specifications High Lumen Output Series Medium Lumen Output Series Input Voltage 120 277V 120 277V Input Power foot complete system 9W 6W Input Frequency 50 60Hz 50 60Hz Power Factor 0 9 0 9 ...

Отзывы: