CHAPTER 4: FUNCTIONALITY
CONFIGURATION SETTINGS
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–29
4.2
Configuration Settings
4.2.1
Overview
An overview of the LM10 programmable parameters is shown below.
Table 4–1: LM10 Programmable Parameters
Parameter
Range/Options
Default
Reference
Control power transformer
CPT ratio
200:120, 240:120, 480:120, 600:120,
2400:120, 3000:120, 3300:120,
4200:120, 4800:120, 5400:120,
6000:120, 7200:120
240:120
page 4–31
Current transformer
CT / sensor pack
27 A Sensor Pack, 90 A Sensor Pack,
75:5, 100:5, 150:5, 200:5, 225:5,
250:5, 300:5, 400:5, 500:5, 600:5,
700:5, 800:5
100:5 Ratio
page 4–31
CT turns
1 to 4 in steps of 1
1
page 4–31
Starter type
FVNR, FVR, RV, 2S1W, 2S2W, Custom
FVNR
page 4–32
FLA (RUN1 and RUN2)
1.2 to 800 A in steps of 0.1
100.0 A
page 4–32
Ground fault level
0.4 to 20 A in steps of 0.2 or Off
Off
page 4–32
Ground fault timeout
0 to 2.5 seconds in steps of 0.1
0.5 sec.
page 4–32
Jam level
100 to 250% of FLA in steps of 1 or
Off
Off
page 4–32
Jam timeout
0 to 1000 seconds in steps of 5
120 sec.
page 4–32
Stall level
330 to 600% of FLA in steps of 5 or
Off
Off
page 4–32
Stall timeout
0 to 30 seconds in steps of 0.5
10 sec.
page 4–32
Current unbalance level
2 to 25% of FLA in steps of 1 or Off
Off
page 4–32
Current unbalance
timeout
0 to 255 seconds in steps of 1
5 sec.
page 4–32
Load loss level
15 to 100% of Full Load in steps of 1
or Off
Off
page 4–32
Load loss timeout
0 to 255 seconds in steps of 1
60 sec.
page 4–32
Undervoltage
96 V fixed (trip delay time 0.5 sec.)
96 V
page 4–34
Overvoltage
140 V fixed (trip delay time 0.5 sec.)
140 V
page 4–34
Aux. sense 1 time delay
Aux. sense 2 time delay
0.1 to 25.0 sec. in steps of 0.1 for ON
state; 0.0 sec. for Disabled
0.4 sec.
page 4–34
Run 1 to Run 2 time delay;
Run 2 to Run 1 time delay
0 to 600 seconds in steps of 1
0 sec.
page 4–34
Under/overvoltage enable
Off, On
On
page 4–34
Maintained input switches
Off = momentary,
On = maintained/latched
Off
page 4–34
Auto restart
Off, On
Off
page 4–34
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...
Страница 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...