CHAPTER 3: INTERFACE
PDU SCREENS AND MENUS
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
3–21
3.2
PDU Screens and Menus
3.2.1
Main Startup Screen
The main startup screen displays the following information. These parameters are not
programmable via serial communications, but rather are displayed for convenience. See
on page 1–4 for setting instructions.
•
PDU software version displayed briefly, then replaced by the LM10 software version
•
Trip class
•
MAC ID
•
Baud rate
3.2.2
History Record and Status Screens
See
on page 3–19 for details on the history record and status screens.
3.2.3
Configuration Menu
See
on page 3–19 for details on the configuration menu list. The configuration
menu is used to set all the programmable parameters outlined in
CTs and CPTs Sub-menu
: This menu and its sub-menus are used to select Control
Power Transformer (CPT), Current Transformer (CT) or Sensor Pack, and the number of
turns through the CT.
•
Starter Type Sub-menu
: This menu is used to select Motor Starter Type.
•
Run 1 and Run 2 Setup Sub-menus
: This Run 1 menu is used to set full load current
(FLA) for Run 1. It also contains sub-menus for enable/disable and configures the
following optional faults: ground fault, jam, stall, current unbalance, and load loss.
Each fault is configurable not only in magnitude, but also in time delay in which that
condition is allowed to exist before the LM10 trips.
The Run 2 Setup menu is laid out identically to Run 1 menu. Unless a custom motor
type is selected, Run 2 setup is not necessary.
The full-load current will auto-populate if “Two-Speed” is selected. 2S1W will provide a
4:1 ratio of the FLA and 2S2W will set the FLA to a 2:1 ratio.
Only one relay at a time can be on.
•
Time Delays Sub-menu
: The following time delays are set using this menu:
Auxiliary sense 1 (contactor closed; opened detects welded contacts)
Auxiliary sense 2 (contactor closed; opened detects welded contacts)
Run 1 to Run 2 (delay between forward and reverse or between speeds)
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...
Страница 106: ...I 4 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL INDEX ...