1–8
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 1: INTRODUCTION
AVERAGE CURRENT
Resolution: .........................................................0.1 A
Range:..................................................................0.05 to 8 × CT Primary (3200.0 A max.)
Accuracy:............................................................±5% of full scale
GROUND CURRENT
Resolution: .........................................................0.1 A
Range:..................................................................0.0 to 25.0 A
Accuracy:............................................................±0.2A when current < 4.0 A
±5% of full scale when current
≥
4.0A
CURRENT UNBALANCE
Resolution: .........................................................1%
Range:..................................................................0 to 250%
Accuracy:............................................................±5% of full scale
VOLTAGE
Resolution: .........................................................1 V
Range:..................................................................0 to 9000 V
Accuracy:............................................................±5% of full scale
POWER
Resolution: .........................................................0.1 kW
Range:..................................................................0 to 6553.5 kW
Accuracy:............................................................±5% of full scale
POWER FACTOR
Resolution: .........................................................0.01
Range:..................................................................0.5 to 1.0
Accuracy:............................................................±5% of full scale
TRIP HISTORY
Trip history:........................................................up to last 10 trips
COUNTERS
Motor run hour counter: .............................up to 65535 hours
1.5.3
Control Functions
STARTER
Starter types:....................................................FVNR, FVR, RV, 2S1W, 2S2W, custom
Power loss autorestart: ...............................restart after power loss of 4 seconds or less
1.5.4
Inputs
POWER SUPPLY
Control power: .................................................80 to 145 V AC
Frequency:.........................................................50 and 60Hz
CURRENT
CT sensor pack: ...............................................NEMA starter size 1 to 6 (27 A, 90 A primary)
Sensor Input:.....................................................0 to 0.27 V AC
Phase CT input:................................................0 to 5 A
Phase CT primary:..........................................75, 100, 120, 150, 200, 225, 250, 300, 400, 500, 600, 700,
800
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...