CHAPTER 10: THEORY OF OPERATION
OVERVIEW
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
10-5
10
10.1.7 Ground differential element
The line ground differential function allows sensitive ground protection for single-line-to-ground faults, allowing the phase
differential element to be set higher (above load) to provide protection for multi-phase faults. The L90 ground differential
function calculates ground differential current from all terminal phase currents. The maximum phase current is used for
the restraint. The L90 is applied in dual-breaker applications to cope with significant through current at remote terminals
that can cause CT errors or saturation.
The line ground differential function uses the same CT matched and time-aligned phasors as the phase-segregated
current differential function. The operate signal is calculated for both real and imaginary parts as follows:
Eq. 10-12
Eq. 10-13
The terms for the second remote terminal are omitted in two-terminal applications.
The maximum through current is available locally and re-constructed from the received remote restraint based on the
maximum remote restraint current shown in the previous section and as indicated as follows.
For two-terminal applications:
Eq. 10-14
For three-terminal applications:
Eq. 10-15
The 87G restraining signal is calculated as follows:
Eq. 10-16
The terms for the second remote terminal are omitted in two-terminal applications.
The operate signal for the ground differential function (I
OP_87G
)
2
is then calculated as:
Eq. 10-17
The restraint signal (I
87G
)
2
is calculated as follows for two-terminal applications:
Eq. 10-18
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...