CHAPTER 7: COMMANDS AND TARGETS
COMMANDS MENU
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
7-3
7
This menu contains commands for clearing historical data such as the event records. Data is cleared by changing a
command setting to “Yes” and pressing the
ENTER
key. After clearing data, the command setting automatically reverts to
“No.”
COMMANDS
CLEAR RECORDS
CLEAR IEC61850 XWSI OPCNT
COMMANDS
CLEAR RECORDS
CLEAR IEC61850 XCBR OPCNT
The Clear XSWI commands clear the disconnect operation counters for each phase and the three-phase counter. Similarly,
the Clear XCBR commands clear the circuit breaker operation counters for each phase and the three-phase counter.
7.1.3 Set date and time
COMMANDS
SET DATE AND TIME
The date and time can be entered on the front panel keypad. The time setting is based on the 24-hour clock. The complete
date, as a minimum, must be entered to allow execution of this command. The new time and date take effect when the
ENTER
key is pressed.
The clock also can be synchronized to the local computer time among several UR devices. Use the
Synchronize Devices
entry in the Online Window area of the EnerVista software. (Click the button at the top of the window that opens.)
When the relay is synchronizing to an external time source such as PTP, IRIG-B, or SNTP, the manually entered time or the
manually synchronized time is over-written.
The timescale of the entered time is local time, including daylight savings time where and when applicable.
7.1.4 Relay maintenance
COMMANDS
RELAY MAINTENANCE
CLEAR IEC61850
XWSI OPCNT
CLEAR XSWI 1
OpCnt? No
Range: No, Yes
CLEAR XSWI 24
OpCnt? No
Range: No, Yes
CLEAR IEC61850
XCBR OPCNT
CLEAR XCBR 1
OpCnt? No
Range: No, Yes
CLEAR XCBR 8
OpCnt? No
Range: No, Yes
COMMANDS
SET DATE AND TIME
SET DATE AND TIME:
2000/01/14 13:47:03
Range: YYYY/MM/DD HH:MM:SS
COMMANDS
RELAY MAINTENANCE
PERFORM LAMP TEST?
No
Range: No, Yes
PERFORM LCD TEST?
Off
Range: Off, Red, Green, Blue, White & Text Pattern,
Black & Text Pattern, TV Test Pattern
PERFORM PUSHBUTTON
TEST? No
Range: No, Yes
UPDATE ORDER CODE?
No
Range: No, Yes
REBOOT RELAY?
No
Range: No, Yes
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...