CHAPTER 5: SETTINGS
TESTING
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-429
5
The Forcible mode is intended for testing involving forcing relay operation by test signal injection and verifying correct
relay output. This mode is also for tests to verify the relay outputs (both contact and communications) have the intended
impact on specific power system devices or on specific other substation automation devices. Contact outputs can be
selectively enabled or forced as described in the following two sections. Shared outputs to bricks have their test mode flag
raised, which results in their value only being accepted by relays also in forcible mode. GOOSE transmissions have the
"simulation" flag set, which results in these only being accepted by other devices that have their "Sim" data attribute set.
The "Sim" data attribute in the relay is set, so that if GOOSE messages are received with the "simulation" flag set, these are
used in place of the normal messages. The quality attribute of values that are output via 61850 MMS services are set to
"valid" + "test," which signals that the values should not be used for operational purposes.
Otherwise, the UR remains fully operational while in the Forcible test mode, allowing for various testing procedures. In
particular, the protection and control elements, and FlexLogic function normally. Other than the IEC 61850 protocol,
communications based inputs and outputs remain fully operational. The test procedure must take this into account. Direct
I/O channel tests and PMU tests are usable on applicable models.
The test mode can be selected either through the front panel, through EnerVista UR Setup, or through IEC 61850 control to
LLN0.Mod. LLN0.Mod.ctlVal "on" selects Disabled, "test/blocked" selects Isolated, and "test" selects Forcible. The
TEST MODE
FUNCTION
setting can only be changed by a direct user command. Following a restart, power up, settings upload, or
firmware upgrade, the test mode remains at the last programmed value. This allows a UR that has been placed in isolated
mode to remain isolated during testing and maintenance activities.
5.11.2 Test mode forcing
SETTINGS
TESTING
TEST MODE FORCING
When in Forcible mode, the operand selected by the
TEST MODE FORCING
setting dictates further response of the L90 to
testing conditions, as described in the following two sections.
The test mode state is indicated on the relay front panel by a combination of the Test Mode LED indicator, the In-Service
LED indicator, and by the critical fail relay, as shown in the following table.
Table 5-45: Test mode operation
5.11.3 Phasor Measurement Unit test values
SETTINGS
TESTING
PMU TEST VALUES
PMU 1 TEST VALUES
TESTING
TEST MODE FORCING:
On
Range: FlexLogic operand
TEST MODE
FUNCTION
In-service
LED
Test mode
LED
Critical fail
relay
TEST MODE
FORCING
Contact input and output behavior
Disabled
Unaffected
Off
Normal
No effect
Normal
Isolated
Off
On
De-energized No effect
Contact outputs disabled
Forcible
Off
Flashing
De-energized Off
Normal
On
Controlled by forcing features
On restart, the
TEST MODE FORCING
setting and the force contact input and force contact output settings revert to
their default states.
PMU 1
TEST VALUES
PMU 1 TEST
FUNCTION: Disabled
Range: Enabled, Disabled
PMU 1 VA TEST
MAGNITUDE: 500.00 kV
Range: 0.00 to 700.00 kV in steps of 0.01
PMU 1 VA TEST
ANGLE: 0.00°
Range: –180.00 to 180.00° in steps of 0.05
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...