CHAPTER 5: SETTINGS
TRANSDUCER INPUTS/OUTPUTS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-425
5
5.10.3 DCmA outputs
SETTINGS
TRANSDUCER I/O
DCMA OUTPUTS
DCMA OUTPUT H1(U8)
Hardware and software is provided to generate DCmA signals that allow interfacing with external equipment. Hardware
details are contained in chapter 3. The DCmA output channels are arranged in a manner similar to transducer input or CT
and VT channels. The user configures individual channels with the settings as follows.
The channels are arranged in sub-modules of two channels, numbered 1 through 8 from top to bottom. On power-up, the
relay automatically generates configuration settings for every channel, based on the order code, in the same manner used
for CTs and VTs. Each channel is assigned a slot letter followed by the row number, 1 through 8 inclusive, which is used as
the channel number.
Both the output range and a signal driving a given output are user-programmable via the following settings menu (an
example for channel M5 is shown).
The relay checks the driving signal (
x
in equations below) for the minimum and maximum limits, and subsequently re-
scales so the limits defined as
MIN VAL
and
MAX VAL
match the output range of the hardware defined as
RANGE
. The
following equation is applied:
Eq. 5-49
where
x is a driving signal specified by the
SOURCE
setting
I
min
and I
max
are defined by the
RANGE
setting
k is a scaling constant calculated as:
Eq. 5-50
The feature is intentionally inhibited if the
MAX VAL
and
MIN VAL
settings are entered incorrectly, for example when
MAX VAL
–
MIN VAL
< 0.1 pu. The resulting characteristic is illustrated in the following figure.
DCMA OUTPUT H1
DCMA OUTPUT H1
SOURCE: Off
Range: Off, any analog actual value parameter
DCMA OUTPUT H1
RANGE: –1 to 1 mA
Range: –1 to 1 mA, 0 to 1 mA, 4 to 20 mA
DCMA OUTPUT H1
MIN VAL: 0.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
DCMA OUTPUT H1
MAX VAL: 1.000 pu
Range: –90.000 to 90.000 pu in steps of 0.001
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...